Z Unidade Modular de Manuseio de Ar
- Configurable Treatment Sections
- Thermal-Break Double Skin
- Low-Leakage Panel Joints
- Service-Friendly Access
Introdução do produto
The modular air handling unit is assembled from matched casing sections around a rigid corrosion-protected frame. Filter banks, chilled-water or direct-expansion coils, heating coils, humidifiers, energy-recovery devices and plug-fan arrays can be placed in the required process order. Smooth internal panels and gasketed access doors support routine cleaning, while thermally separated skins limit condensation on the outer casing. Shipping splits allow large units to pass through plant-room access routes without sacrificing a continuous sealed air path after assembly.
Características-chave
Double-skin insulated panels reduce casing heat gain, radiated fan noise and surface condensation risk.
Gasketed block joints and access doors maintain a controlled air path while permitting component replacement.
Direct-drive plug fans or fan arrays provide stable airflow control without belts in the supply airstream.
Preocupações do produto do cliente
A cleanroom air handler must fit the building, deliver the scheduled treatment sequence and remain accessible without creating uncontrolled leakage paths.
Aplicações típicas
Parâmetros técnicos
Typical construction ranges for a configurable cleanroom modular air-handling unit are listed below.
| Material principal | Rigid polyurethane foam or high-density mineral-wool insulation within double-skin casing panels |
|---|---|
| Painel de espessura | 50–70 mm insulated double-skin casing |
| Largura efetiva | 1000–4000 mm nominal casing width |
| Comprimento máximo | Up to 12000 mm assembled length using bolted shipping sections |
| Aço enfrentando espessura | 0.5–1.0 mm inner and outer sheet, selected by casing duty |
| Densidade Core | 40–45 kg/m³ polyurethane or 80–120 kg/m³ mineral wool |
| Condutividade térmica | 0.022–0.040 W/(m·K), depending on insulation material |
| Superfície acabado | Powder-coated galvanized outer skin with galvanized or 304 stainless-steel cleanable inner skin |
| Tipo conjunto | Thermal-break aluminum frame with compression-gasketed panel and block joints |
| Customização | Disponível com base na aplicação pretendida e no ambiente operacional. |
Opções disponíveis
Planning a Modular Air Handling Unit specification?
Envie-nos as suas dimensões, condições de instalação, metas de desempenho e acabamento de superfície necessário.

Inglês
Alemão
Língua árabe
Francês
Língua indonésia
Japonês
Coreano
Língua malaia
Portuguêsatual
Língua russa
Espanhol
Tailandês
Língua turca
Vietnã