The modular air handling unit is assembled from matched casing sections around a rigid corrosion-protected frame. Filter banks, chilled-water or direct-expansion coils, heating coils, humidifiers, energy-recovery devices and plug-fan arrays can be placed in the required process order. Smooth internal panels and gasketed access doors support routine cleaning, while thermally separated skins limit condensation on the outer casing. Shipping splits allow large units to pass through plant-room access routes without sacrificing a continuous sealed air path after assembly.
Características clave
Double-skin insulated panels reduce casing heat gain, radiated fan noise and surface condensation risk.
Gasketed block joints and access doors maintain a controlled air path while permitting component replacement.
Direct-drive plug fans or fan arrays provide stable airflow control without belts in the supply airstream.
Preocupaciones del producto del cliente
A cleanroom air handler must fit the building, deliver the scheduled treatment sequence and remain accessible without creating uncontrolled leakage paths.
Aplicaciones típicas
Parámetros técnicos
Typical construction ranges for a configurable cleanroom modular air-handling unit are listed below.
| Materiales Core | Rigid polyurethane foam or high-density mineral-wool insulation within double-skin casing panels |
|---|---|
| Panel de espesor | 50–70 mm insulated double-skin casing |
| Ancho efectivo | 1000–4000 mm nominal casing width |
| Longitud máxima | Up to 12000 mm assembled length using bolted shipping sections |
| Acero frente a espesor | 0.5–1.0 mm inner and outer sheet, selected by casing duty |
| Densidad Core | 40–45 kg/m³ polyurethane or 80–120 kg/m³ mineral wool |
| Conductividad térmica | 0.022–0.040 W/(m·K), depending on insulation material |
| Superficie acabada | Powder-coated galvanized outer skin with galvanized or 304 stainless-steel cleanable inner skin |
| Tipo conjunto | Thermal-break aluminum frame with compression-gasketed panel and block joints |
| Customization | Disponible según la aplicación prevista y el entorno operativo. |
Opciones disponibles
Planning a Modular Air Handling Unit specification?
Envíenos sus dimensiones, condiciones de instalación, objetivos de rendimiento y acabado superficial requerido.

Inglés
Alemán
El árabe
Francés
Idioma indonesio
El japonés
Coreano
El malayo
El portugués
El ruso
EspañolCurrent
Tailandés
El turco
El vietnamita