A locking quadrant damper with linked galvanized blades for setting and retaining the balancing position of a rectangular duct branch.
  • Locking Manual Quadrant
  • Opposed 3V Blade Bank
  • Concealed Frame Linkage
  • Permanent Branch Balancing
طلب عرض أسعار تصفح المنتجات

مقدمة المنتج

The manual volume control damper places a bank of linked 3V blades inside a rigid galvanized channel frame. Turning the external quadrant rotates the blade shafts together, allowing the balancing technician to establish the required branch resistance and then lock the position mechanically. Opposed blade motion provides more even downstream velocity distribution than a single flap at intermediate positions. The drive linkage is enclosed within the frame, leaving the airway clear and protecting moving parts from accidental contact.

الخصائص الرئيسية

A graduated locking quadrant retains the selected blade angle without electrical power or control wiring.

Opposed 3V blades divide the throttling area across the full frame for smoother branch balancing.

Concealed linkage reduces obstruction in the airway and shields connecting bars from handling damage.

Channel-frame flange options support duct insertion, surface mounting or connection to an equipment opening.

مخاوف المنتج للعملاء

A manual damper should give the balancer fine position control, remain locked after commissioning and avoid creating a severely biased downstream velocity profile.

A loose handle creeps open after the branch has been balanced.A positive locking quadrant clamps the shaft at the recorded blade position.
A single large blade sends a concentrated jet toward one side of the downstream duct.Opposed blade operation divides the opening and produces a more distributed throttled flow.
External linkage is bent by insulation work or routine ceiling access.Link bars concealed inside the channel frame leave only the protected operator outside the casing.
The adjustment handle becomes buried beneath duct insulation.An extended shaft and stand-off quadrant preserve visible, reachable adjustment after insulation is applied.

تطبيقات نموذجية

Cleanroom supply branch balancingGeneral exhaust duct commissioningAir-handling unit internal bypassesReturn-air grille branch controlFixed-volume process ventilation

المعلمات الفنية

Typical construction data for a galvanized rectangular manual balancing damper are listed below.

المواد الأساسيةGalvanized-steel 3V blades with plated steel shafts, concealed linkage and polymer bearings
سمك اللوحة1.5 mm formed galvanized control blades
العرض الفعال152–1219 mm nominal single-section frame width
الحد الأقصى الطولUp to 1880 mm single-section frame height
الصلب يواجه سمك1.5 mm galvanized channel frame
الكثافة الأساسيةApproximately 7850 kg/m³ for galvanized steel blades
الموصلية الحراريةApproximately 45–55 W/(m·K) for the carbon-steel blade material
إنهاء السطحMill-galvanized blade and frame surfaces with zinc-plated operating hardware
نوع المشتركFlanged channel frame with linked opposed blades and external locking quadrant
التخصيصمتوفر على أساس التطبيق المقصود وبيئة التشغيل.

الخيارات المتاحة

Parallel or opposed blade actionSingle, reversed or double flange frameExtended shaft for insulated ducts304 or 316 stainless-steel construction

Planning a Manual Volume Control Damper specification?

أرسل لنا الأبعاد الخاصة بك، شروط التثبيت، أهداف الأداء والتشطيب السطحي المطلوب.

تحدث مع فريقنا
E البريد الإلكتروني لنا WhatsApp WeChat

الرئيسية

المنتجات

الأخبار

من نحن

اتصل بنا