商品紹介
The manual volume control damper places a bank of linked 3V blades inside a rigid galvanized channel frame. Turning the external quadrant rotates the blade shafts together, allowing the balancing technician to establish the required branch resistance and then lock the position mechanically. Opposed blade motion provides more even downstream velocity distribution than a single flap at intermediate positions. The drive linkage is enclosed within the frame, leaving the airway clear and protecting moving parts from accidental contact.
主要な特徴
Opposed 3V blades divide the throttling area across the full frame for smoother branch balancing.
Concealed linkage reduces obstruction in the airway and shields connecting bars from handling damage.
Channel-frame flange options support duct insertion, surface mounting or connection to an equipment opening.
お客様の製品に関する懸念事項
A manual damper should give the balancer fine position control, remain locked after commissioning and avoid creating a severely biased downstream velocity profile.
典型的な用途
技術的なパラメータ
Typical construction data for a galvanized rectangular manual balancing damper are listed below.
| コア材料 | Galvanized-steel 3V blades with plated steel shafts, concealed linkage and polymer bearings |
|---|---|
| パネルの厚さ | 1.5 mm formed galvanized control blades |
| 有効幅 | 152–1219 mm nominal single-section frame width |
| 最大長さ | Up to 1880 mm single-section frame height |
| 鋼鉄の厚さを直面する | 1.5 mm galvanized channel frame |
| コア密度 | Approximately 7850 kg/m³ for galvanized steel blades |
| 熱伝導率 | Approximately 45–55 W/(m·K) for the carbon-steel blade material |
| 表面仕上げ | Mill-galvanized blade and frame surfaces with zinc-plated operating hardware |
| ジョイントタイプ | Flanged channel frame with linked opposed blades and external locking quadrant |
| カスタマイズ | 意図したアプリケーションと動作環境に基づいて利用できます。 |
利用可能なオプション
Planning a Manual Volume Control Damper specification?
寸法、設置条件、性能目標、必要な表面仕上げをお送りください。