Seu fornecedor único para equipamentos de sala limpa e instalações assépticas essenciaisApoio Internacional a Projetos
Open mobile navigationClose mobile navigation
Equipamento de manuseio de ar e HVAC para sala limpa

Coil de resfriamento de água

A deep-row finned coil that cools and dehumidifies cleanroom air using centrally supplied chilled water and controlled condensate drainage.
  • Sensible and Latent Cooling
  • Hydrophilic Fin Surface
  • Insulated Water Headers
  • Stainless Condensate Drainage
Solicite um orçamento. Browse produtos

Introdução do produto

Chilled water circulates through multiple copper-tube rows while warm air crosses blue hydrophilic aluminum fins. When the fin temperature drops below dew point, moisture condenses and drains into a stainless pan beneath the coil. Counterflow circuiting, sufficient face area and controlled fin spacing balance latent performance, water velocity and air pressure drop for cleanroom humidity control.

Características-chave

Deep multi-row construction provides both sensible cooling and moisture removal at controlled face velocity.

Hydrophilic fin treatment encourages condensate to form a thin draining film instead of bridging between fins.

Insulated supply and return headers limit external sweating in the AHU casing.

A sloped stainless drain pan captures condensate and exposes the drain outlet for cleaning.

Preocupações do produto do cliente

Cooling coils must remove moisture without carrying droplets downstream or creating stagnant condensate zones.

High face velocity pulls condensate off the coil into downstream filters.Adequate face area and an optional droplet eliminator keep carryover below the design airflow.
Water retained between fins supports fouling and odor.Hydrophilic coating and a properly pitched coil encourage rapid drainage into the pan.
Uninsulated headers sweat outside the drain-pan footprint.Closed-cell header insulation directs any surface moisture toward contained drainage areas.
Poor circuit balance leaves warm streaks in supply air.Matched circuits and full-width headers distribute chilled water uniformly across the face.

Aplicações típicas

Pharmaceutical cleanroom air handlersLow-dew-point make-up air unitsElectronics manufacturing HVACHospital surgical-suite AHUsLaboratory humidity control

Parâmetros técnicos

Typical physical construction ranges for a cleanroom chilled-water coil are summarized below.

Material principalCopper tubes with blue hydrophilic aluminum fins and insulated copper headers
Painel de espessura1.5-2.0 mm stainless or galvanized coil casing
Largura efetiva400-3000 mm active fin face width
Comprimento máximoUp to 4200 mm overall coil and drain-pan length
Aço enfrentando espessura1.0-1.5 mm 304 stainless condensate pan
Densidade CoreBase-metal density approximately 2730 kg/m³ for the hydrophilic-coated 3003 aluminum cooling fins
Condutividade térmicaBase-metal thermal conductivity approximately 193 W/(m·K) for the coated aluminum cooling fins
Superfície acabadoBlue hydrophilic-coated aluminum fins with stainless drain pan
Tipo conjuntoBrazed copper circuits in flanged casing with threaded or flanged headers and welded drain pan
CustomizaçãoDisponível com base na aplicação pretendida e no ambiente operacional.

Opções disponíveis

Four to twelve tube rowsHydrophilic, epoxy or corrosion-resistant fin coatingStainless casing and double-slope drain panMoisture eliminator and insulated header enclosure

Planning a Chilled-Water Cooling Coil specification?

Envie-nos as suas dimensões, condições de instalação, metas de desempenho e acabamento de superfície necessário.

Fale com a nossa equipe
Email-nos O WhatsApp WeChat