Equipamento de descontaminação de pessoal e materiais
Pressão positiva limpa transferência caixa de passagem
A filtered-supply pass box maintained above adjacent pressure to reduce inward contamination towards sensitive payloads.
- Positive Chamber Bias
- Filtered Supply Air
- Controlled Relief Path
- Timed Clean-Air Purge
Introdução do produto
The positive-pressure transfer pass box supplies more filtered air than leaves through its controlled relief path, moving small leakage outwards instead of drawing room particles towards the payload. A fan, diffuser and pressure sensor maintain the selected chamber condition. Receiving-side access can be delayed until a purge and pressure recovery have completed.
Características-chave
A defined relief path avoids reliance on door-gap leakage.
A full-width diffuser distributes clean air across trays and containers.
Pressure indication supports operational checks before release.
A timed purge clears loading-side air before clean-side access.
Preocupações do produto do cliente
Payload protection requires outward leakage control without excessive door force or uncontrolled airflow to adjacent rooms.
Room particles enter through minor gasket imperfections.Filtered positive bias drives leakage outward from the protected payload zone.
High pressure strains latches and complicates closing.A controlled relief path limits chamber pressure rise.
A narrow jet bypasses the load and leaves corners stagnant.A broad diffuser spreads supply air over the chamber.
The receiving door opens before loading-side air is displaced.A purge timer and pressure permissive control release.
Aplicações típicas
Sterile component protectionOptics and sensor transferMicroelectronics materialsMedical-device assembly
Parâmetros técnicos
Representative clean-air construction ranges for a positive-pressure transfer pass box are shown below.
| Material principal | SUS 304 or SUS 316L chamber with variable-speed filtered supply fan, diffuser and relief path |
|---|---|
| Painel de espessura | 80-150 mm supply-plenum and double-wall construction |
| Largura efetiva | 500-1200 mm clear transfer width |
| Comprimento máximo | Up to 1500 mm chamber depth |
| Aço enfrentando espessura | 1.0-1.5 mm stainless-steel facing |
| Densidade Core | 35-40 kg/m³ polyurethane insulation around supply and relief plenums |
| Condutividade térmica | 0.022-0.028 W/(m·K) for polyurethane plenum insulation |
| Superfície acabado | Brushed stainless chamber with smooth diffuser and removable payload shelf |
| Tipo conjunto | Sealed cabinet seams with interlocked compression doors, gasketed filter frame and relief connection |
| Customização | Disponível com base na aplicação pretendida e no ambiente operacional. |
Opções disponíveis
Typical +10 to +30 Pa pressure rangeH13 or H14 supply filterConstant-pressure EC fan controlFiltered or ducted relief connection
Planning a Positive-Pressure Clean Transfer Pass Box specification?
Envie-nos as suas dimensões, condições de instalação, metas de desempenho e acabamento de superfície necessário.

Inglês
Alemão
Língua árabe
Francês
Língua indonésia
Japonês
Coreano
Língua malaia
Portuguêsatual
Língua russa
Espanhol
Tailandês
Língua turca
Vietnã