Canal Base de Parede de Sala Limpa

A galvanized-steel or aluminum floor track that locates modular cleanroom wall panels, transfers base loads and creates a level, sealable interface above the finished floor.
  • Level Panel Support
  • Direct Floor Anchorage
  • Sealed Base Interface
  • Demountable Wall Compatible
Solicite um orçamento. Browse produtos

Introdução do produto

Cleanroom Wall Base Channel is the structural floor track beneath a modular wall run. The channel establishes panel alignment, restrains lateral movement at the base and distributes the wall load to the slab. Lightweight formed-steel versions provide a simple head-and-base track, while adjustable two-part aluminum systems can compensate for floor variation and create a flush recess for resilient or resin flooring. Mechanical anchors secure the lower section and hygienic sealant closes the floor and panel interfaces, leaving the visible room junction ready for coving or a recessed floor return.

Características-chave

A continuous track keeps the first wall course straight and controls panel position along the floor.

Mechanical floor anchors transfer base restraint independently of sealant adhesion.

Adjustable aluminum variants compensate for uneven slabs before wall panels are installed.

Recessed configurations accept a flush vinyl or resin floor cove without an exposed ledge.

Demountable wall panels can be removed while the base alignment system remains in place.

Preocupações do produto do cliente

The base channel must keep the wall level, accommodate the selected floor finish and remain sealed where the partition meets the slab.

An uneven slab causes cumulative panel misalignment higher in the wall.An adjustable base interface or controlled packing establishes a level bearing line before panels are set.
Sealant alone cannot safely restrain movement at the foot of a tall partition.Mechanical anchors secure the channel directly to the structural floor.
A projecting track creates a ledge beside sheet flooring.A recessed base detail receives the floor cove flush with the cleanroom wall face.
Cleaning liquid can enter through an unsealed floor-track joint.Continuous sealant beneath the track and along the panel interface closes both leakage paths.

Aplicações típicas

Modular cleanroom wall foundationsPharmaceutical partition basesModular laboratory partition foundationsFood-production hygienic wallsSemiconductor cleanroom enclosures

Parâmetros técnicos

Typical cleanroom wall base channel construction ranges are shown below.

Material principal6063 aluminum extrusion or formed galvanized/stainless steel
Painel de espessura0.5–2.5 mm channel wall thickness
Largura efetiva50, 75 or 100 mm panel seat width
Comprimento máximo3000–6000 mm per section
Aço enfrentando espessura0.5–1.0 mm for formed steel channel; N/A for aluminum version
Densidade CoreN/A — formed channel has no insulation core
Condutividade térmicaN/A — structural floor track, not an insulating panel
Superfície acabadoGalvanized, brushed stainless steel, anodized aluminum or powder-coated aluminum
Tipo conjuntoMechanically anchored floor track with sealed panel seat and flooring interface
CustomizaçãoDisponível com base na aplicação pretendida e ambiente operacional

Opções disponíveis

Fixed formed channelAdjustable two-part aluminum baseRecess for 2 mm vinyl flooringStainless steel or color-matched finish