A ventilation air system that independently controls outdoor-air moisture and temperature before delivering a measured dry-air quantity to clean spaces.
  • Independent Latent Control
  • Measured Ventilation Air
  • Energy-Recovery Ready
  • Stable Dry Supply Air
Запрос котировки Просмотреть продукты

Введение продукции

A dedicated outdoor air system separates ventilation and latent treatment from the high recirculation airflow used for cleanroom particle control. It receives 100% outdoor air, recovers useful energy from a separated exhaust stream where appropriate, cools and dries the air, then reheats it to a neutral or designed supply condition. This division lets terminal recirculation units handle sensible load and filtration without relying on them to remove the full outdoor-air moisture load. Airflow, dew point and supply temperature can be monitored independently.

Основные характеристики

Ventilation airflow is measured independently from cleanroom recirculation air changes.

Deep dehumidification establishes a predictable supply dew point across seasonal outdoor conditions.

Plate, run-around or carefully selected rotary recovery can reduce outdoor-air heating and cooling load.

Reheat prevents overcooled ventilation air from causing local discomfort or excess sensible cooling.

Обеспокоенность клиентов продуктами

When ventilation air and recirculation air are treated together, moisture control can drift as outdoor conditions and room sensible loads change independently.

The cleanroom becomes humid at low sensible load even though space temperature is stable.The DOAS controls outdoor-air dew point separately from room recirculation cooling.
Ventilation quantity is inferred from a damper position rather than measured.An airflow station and fan control maintain the scheduled outdoor-air volume.
Energy recovery risks transferring contaminants from exhaust to supply.A separated plate or run-around system is selected where cross-stream leakage cannot be accepted.
Cold dry ventilation air overcools perimeter or low-load rooms.Modulating reheat delivers a neutral or scheduled supply-air temperature after dehumidification.

Типичные приложения

Pharmaceutical cleanroom ventilationLaboratory outdoor-air systemsMedical and research facilitiesHigh-humidity industrial locationsHealthcare clean zones

Технические параметры

Typical double-skin construction for a cleanroom dedicated outdoor air system is listed below.

Основной материалClosed-cell polyurethane insulation in thermally separated double-skin panels
Толщина панели50–70 mm insulated casing
эффективная ширина1000–3400 mm nominal casing width
Максимальная длинаUp to 12000 mm including recovery, coil, reheat and fan modules
Толщина линий стали0.6–1.0 mm outer skin and 0.8–1.0 mm wet-section lining
Плотность ядра40–45 kg/m³ closed-cell polyurethane
Теплопроводимость0.022–0.026 W/(m·K) for the casing insulation
Поверхностная отделкаPowder-coated exterior with cleanable galvanized or stainless inner surfaces
Объединенный типCompression-gasketed thermal-break panels with isolated supply and exhaust air paths
CustomizationДоступно в зависимости от предполагаемого применения и операционной среды.

Доступные варианты

Plate, rotary or run-around heat recoveryChilled-water, DX or heat-pump dehumidificationHot-gas, water or electric reheatSteam or adiabatic winter humidification