Nhà cung cấp một cửa của bạn cho thiết bị phòng sạch và thiết bị vô trùng cơ sở thiết yếuHỗ trợ dự án quốc tế
Open mobile navigationClose mobile navigation
Thiết bị xử lý không khí và HVAC phòng sạch

Hệ thống không khí ngoài trời chuyên dụng

A ventilation air system that independently controls outdoor-air moisture and temperature before delivering a measured dry-air quantity to clean spaces.
  • Independent Latent Control
  • Measured Ventilation Air
  • Energy-Recovery Ready
  • Stable Dry Supply Air
Yêu cầu báo giá Duyệt các sản phẩm

Giới thiệu Sản phẩm

A dedicated outdoor air system separates ventilation and latent treatment from the high recirculation airflow used for cleanroom particle control. It receives 100% outdoor air, recovers useful energy from a separated exhaust stream where appropriate, cools and dries the air, then reheats it to a neutral or designed supply condition. This division lets terminal recirculation units handle sensible load and filtration without relying on them to remove the full outdoor-air moisture load. Airflow, dew point and supply temperature can be monitored independently.

Các tính năng chính

Ventilation airflow is measured independently from cleanroom recirculation air changes.

Deep dehumidification establishes a predictable supply dew point across seasonal outdoor conditions.

Plate, run-around or carefully selected rotary recovery can reduce outdoor-air heating and cooling load.

Reheat prevents overcooled ventilation air from causing local discomfort or excess sensible cooling.

Các mối quan tâm về sản phẩm của khách hàng

When ventilation air and recirculation air are treated together, moisture control can drift as outdoor conditions and room sensible loads change independently.

The cleanroom becomes humid at low sensible load even though space temperature is stable.The DOAS controls outdoor-air dew point separately from room recirculation cooling.
Ventilation quantity is inferred from a damper position rather than measured.An airflow station and fan control maintain the scheduled outdoor-air volume.
Energy recovery risks transferring contaminants from exhaust to supply.A separated plate or run-around system is selected where cross-stream leakage cannot be accepted.
Cold dry ventilation air overcools perimeter or low-load rooms.Modulating reheat delivers a neutral or scheduled supply-air temperature after dehumidification.

Các ứng dụng điển hình

Pharmaceutical cleanroom ventilationLaboratory outdoor-air systemsMedical and research facilitiesHigh-humidity industrial locationsHealthcare clean zones

Thông số kỹ thuật

Typical double-skin construction for a cleanroom dedicated outdoor air system is listed below.

Vật liệu lõiClosed-cell polyurethane insulation in thermally separated double-skin panels
Độ dày bảng điều khiển50–70 mm insulated casing
Chiều rộng hiệu quả1000–3400 mm nominal casing width
Chiều dài tối đaUp to 12000 mm including recovery, coil, reheat and fan modules
Thép đối mặt với độ dày0.6–1.0 mm outer skin and 0.8–1.0 mm wet-section lining
Mật độ lõi40–45 kg/m³ closed-cell polyurethane
Độ dẫn nhiệt0.022–0.026 W/(m·K) for the casing insulation
Kết thúc bề mặtPowder-coated exterior with cleanable galvanized or stainless inner surfaces
Loại khớp nốiCompression-gasketed thermal-break panels with isolated supply and exhaust air paths
Tùy chỉnhCó sẵn dựa trên ứng dụng dự định và môi trường hoạt động.

Các tùy chọn có sẵn

Plate, rotary or run-around heat recoveryChilled-water, DX or heat-pump dehumidificationHot-gas, water or electric reheatSteam or adiabatic winter humidification

Planning a Dedicated Outdoor Air System specification?

Gửi cho chúng tôi kích thước của bạn, điều kiện lắp đặt, mục tiêu hiệu suất và bề mặt yêu cầu hoàn thiện.

Nói chuyện với đội ngũ của chúng tôi
Email cho chúng tôi WhatsApp WeChat