Système d'air extérieur dédié
- Independent Latent Control
- Measured Ventilation Air
- Energy-Recovery Ready
- Stable Dry Supply Air
Introduction de produit
A dedicated outdoor air system separates ventilation and latent treatment from the high recirculation airflow used for cleanroom particle control. It receives 100% outdoor air, recovers useful energy from a separated exhaust stream where appropriate, cools and dries the air, then reheats it to a neutral or designed supply condition. This division lets terminal recirculation units handle sensible load and filtration without relying on them to remove the full outdoor-air moisture load. Airflow, dew point and supply temperature can be monitored independently.
Key Features
Deep dehumidification establishes a predictable supply dew point across seasonal outdoor conditions.
Plate, run-around or carefully selected rotary recovery can reduce outdoor-air heating and cooling load.
Reheat prevents overcooled ventilation air from causing local discomfort or excess sensible cooling.
Préoccupations du client produit
When ventilation air and recirculation air are treated together, moisture control can drift as outdoor conditions and room sensible loads change independently.
Les applications typiques
Paramètres techniques
Typical double-skin construction for a cleanroom dedicated outdoor air system is listed below.
| Matériaux de base | Closed-cell polyurethane insulation in thermally separated double-skin panels |
|---|---|
| Panneau épaisseur | 50–70 mm insulated casing |
| Largeur effective | 1000–3400 mm nominal casing width |
| Longueur maximale | Up to 12000 mm including recovery, coil, reheat and fan modules |
| Acier face épaisseur | 0.6–1.0 mm outer skin and 0.8–1.0 mm wet-section lining |
| Densité Core | 40–45 kg/m³ closed-cell polyurethane |
| Conductivité thermique | 0.022–0.026 W/(m·K) for the casing insulation |
| surface finie | Powder-coated exterior with cleanable galvanized or stainless inner surfaces |
| Type joint | Compression-gasketed thermal-break panels with isolated supply and exhaust air paths |
| Customisation | Disponible en fonction de l'application prévue et de l'environnement d'exploitation. |
Options disponibles
Planning a Dedicated Outdoor Air System specification?
Envoyez-nous vos dimensions, conditions d'installation, objectifs de performance et finition de surface requise.