Fresh Air Dehidification Unit (Temiz Hava Dehidifikasyon Ünitesi)
- 100 Percent Outdoor-Air Treatment
- Cooling Plus Desiccant Drying
- Recovered Condenser Heat
- Cleanroom Pressure Support
Ürün tanıtımı
The fresh-air dehumidification unit treats the ventilation and replacement air that creates the largest seasonal latent load in many cleanrooms. A prefilter and cooling coil remove heat and bulk moisture, the desiccant section lowers the dew point, and recovered condenser or reactivation heat tempers the leaving air. Weather-resistant louvers, drainable coil sections and pressure-capable fans allow the unit to supply dry make-up air without burdening the recirculation AHU.
Ana Özellikler
Mechanical cooling handles high-temperature bulk condensation while the desiccant stage addresses the remaining vapor load.
Recovered refrigeration heat can temper overcooled air and reduce separate reheat energy.
Low-leakage dampers and variable-speed supply control maintain the scheduled make-up airflow as filters load.
Müşteri Ürün Sorunları
Untreated outdoor air can overwhelm the sensible and latent capacity of a cleanroom recirculation unit, especially during humid weather.
Tipik uygulamalar
Teknik parametreler
Typical casing and dimensional ranges for a packaged cleanroom fresh-air dehumidification unit are shown below.
| Temel malzemeler | Cooling coil and desiccant rotor in a mineral-wool-insulated galvanized steel air-handling casing |
|---|---|
| Panel kalınlığı | 40-60 mm double-skin insulated casing panel thickness |
| Effective Width (Etkili Genişlik) | 1200-3500 mm nominal outdoor-air unit width |
| Maksimum uzunluk | Up to 7500 mm including intake filtration cooling rotor and supply-fan sections |
| Çelik yüz yüze kalınlığı | 0.8-1.2 mm pre-painted outer skin and galvanized or stainless inner skin |
| Core Density (Çekirdek Yoğunluğu) | 45-80 kg/m³ typical mineral-wool casing insulation density |
| Termal İletkenlik | Approximately 0.035-0.045 W/(m·K) for mineral-wool casing insulation |
| Yüzey bitirme | White weather-resistant powder coating with light-blue service doors and stainless wet-section surfaces |
| Ortak tip | Bolted gasketed casing modules with flanged duct openings, flexible fan connections and welded drain pan |
| Customization (Özelleşme) | Kullanılan uygulama ve çalışma ortamına göre kullanılabilir. |
Mevcut Seçenekler