Su proveedor de ventanilla única para equipos de sala limpia y elementos esenciales para instalaciones asépticasApoyo a proyectos internacionales
Open mobile navigationClose mobile navigation
Inicio / Productos / Filtro de aire y filtración química / Side-Access HEPA Filter Housing
Filtro de aire y filtración química

Caja de filtro HEPA de acceso lateral por

A duct-mounted cabinet with removable side doors and a positive-pressure clamping mechanism for servicing HEPA filters from either side.
  • Dual-Side Service
  • Positive Crank Seal
  • Integrated Prefilter Track
  • Welded Weatherproof Cabinet
Solicite un presupuesto. Browse productos

Introducción del producto

This housing positions HEPA or ULPA filters perpendicular to the duct and allows them to slide in from either side. A crank or lever mechanism transfers force evenly to each filter gasket, producing a repeatable seal without access from the air face. Removable gasketed doors close both service openings, and an upstream track accepts a shallow prefilter. Standing flanges, pressure taps and challenge ports simplify integration into clean manufacturing and healthcare air systems.

Características clave

Dual access doors permit service from the side with safe working clearance.

A spring-loaded crank mechanism distributes sealing pressure across each filter row.

The separate prefilter track protects the absolute filter from coarse loading.

External pressure ports support differential-pressure monitoring without opening the cabinet.

Preocupaciones del producto del cliente

A ducted HEPA bank must be serviceable in a narrow plantroom while maintaining uniform gasket compression.

Only one side of the filter bank remains reachable after installation.Removable doors on both sides allow the usable service direction to be selected on site.
Hand-tightened clips apply unequal pressure around a large HEPA gasket.The crank mechanism applies coordinated sealing force across the filter row.
Coarse dust shortens expensive HEPA filter life.An integral prefilter track captures larger particles before the final filter.
A door seal leaks after repeated maintenance cycles.Square reinforced doors and high-memory perimeter gasketing maintain contact around the opening.

Aplicaciones típicas

Cleanroom air-handler final filtrationHospital supply and exhaust systemsPharmaceutical HVAC branchesLaboratory ventilationOutdoor equipment filter sections

Parámetros técnicos

Representative materials and dimensions for a ducted side-access HEPA housing are listed below.

Materiales CoreWelded galvanized or 304 stainless-steel cabinet with steel filter tracks and crank clamp
Panel de espesor1.5–2.0 mm all-welded housing panels
Ancho efectivo365–3920 mm for half- to six-filter-wide assemblies
Longitud máximaUp to 3920 mm bank length in modular multi-filter arrangements
Acero frente a espesor1.5–2.0 mm galvanized or 304 stainless steel
Densidad CoreApproximately 7850 kg/m³ for galvanized-steel cabinet components
Conductividad térmicaApproximately 45–60 W/(m·K) for galvanized-steel construction
Superficie acabadaMill-galvanized, brushed stainless steel or weather-resistant powder coat
Tipo conjuntoStanding duct flanges, dual gasketed access doors and crank-compressed filter gasket
CustomizationDisponible según la aplicación prevista y el entorno operativo.

Opciones disponibles

Galvanized or 304 stainless steelGasket- or gel-seal filter rackTwo-inch prefilter trackChallenge injection and scan ports

Planning a Side-Access HEPA Filter Housing specification?

Envíenos sus dimensiones, condiciones de instalación, objetivos de rendimiento y acabado superficial requerido.

Habla con nuestro equipo
E-mail Nos WhatsApp WeChat