Su proveedor de ventanilla única para equipos de sala limpia y elementos esenciales para instalaciones asépticasApoyo a proyectos internacionales
STSTjh CleanroomOpen mobile navigationClose mobile navigation
Filtro de aire y filtración química

Pre-filtro pre-filtro por

A wire-supported pleated panel that increases coarse-media area and dust capacity without increasing the face size of the filter track.
  • Expanded Media Area
  • Wire-Stabilized Pleats
  • Moisture-Resistant Frame
  • Standard Filter-Track Sizes
Solicite un presupuesto. Browse productos

Introducción del producto

The pleated pre-filter forms cotton-synthetic or fully synthetic media into evenly spaced radial pleats over a corrosion-resistant downstream wire grid. The pleat geometry adds media area and dust storage within a familiar panel footprint. Adhesive bonds between the media, support grid and enclosing frame stop pleats from collapsing or fluttering at high airflow. Standard 25, 50 and 100 mm nominal depths allow the filter to replace flat throwaway panels while providing a longer service interval.

Características clave

Radial pleats place more active media in the same frontal area than a flat pad.

A corrosion-resistant expanded-wire backing prevents pleat collapse and media oscillation.

Diagonal frame members protect pleat geometry during transport and filter changes.

Multiple nominal depths balance available track space, resistance and dust-holding capacity.

Preocupaciones del producto del cliente

Pleated prefilters perform best when pleat spacing remains open and the panel seals evenly against the filter rack.

Flat pads require replacement before their full face area has stored much dust.The pleated pack multiplies usable media area and distributes deposited particles across deeper folds.
Closely packed pleats touch each other and create high-resistance dead zones.Controlled radial spacing keeps adjacent pleat walls separated throughout the panel.
Fan starts pull unsupported media downstream and permanently distort the pack.A bonded expanded-wire grid stabilizes the media on the air-exit side.
Humid intake air softens ordinary frames and opens bypass gaps at the corners.A high wet-strength frame with bonded mitered corners retains shape in normal HVAC humidity.

Aplicaciones típicas

Air-handler prefilter banksRooftop and packaged HVAC unitsFan-coil return-air cabinetsProtection for medium-efficiency bag filtersCommercial and light-process ventilation

Parámetros técnicos

Typical construction ranges for a standard-capacity pleated HVAC pre-filter are shown below.

Materiales CoreCotton-synthetic blend or 100% synthetic mechanical filter media on expanded-wire backing
Panel de espesor22, 45 or 95 mm actual depth for nominal 25, 50 or 100 mm filters
Ancho efectivo289-610 mm standard face width
Longitud máximaUp to 610 mm standard face length
Acero frente a espesor0.30-0.45 mm corrosion-resistant expanded-wire media support
Densidad CoreApproximately 30-60 kg/m³ nominal pleated-media bulk density
Conductividad térmicaApproximately 0.035-0.045 W/(m·K) for dry cotton-synthetic media
Superficie acabadaWhite synthetic media with galvanized or corrosion-resistant support grid
Tipo conjuntoPleated media and wire grid bonded into a moisture-resistant diagonal-support panel frame
CustomizationDisponible según la aplicación prevista y el entorno operativo.

Opciones disponibles

ISO Coarse and MERV 8 grades22 mm, 45 mm or 95 mm actual frame depthMoisture-resistant board, ABS or galvanized-steel frameStandard- or high-capacity radial pleat count

Planning a Pleated Pre-Filter specification?

Envíenos sus dimensiones, condiciones de instalación, objetivos de rendimiento y acabado superficial requerido.

Habla con nuestro equipo
E-mail Nos WhatsApp WeChat