Unidade de Recuperação de Energia Heat-Pipe
- Hermetically Sealed Copper Circuits
- Integral Air-Stream Divider
- Up to Eight Tube Rows
- Serviceable Finned Faces
Introdução do produto
The heat-pipe energy recovery unit extends individually charged copper circuits through two finned sections located in adjacent supply and exhaust ducts. Working fluid evaporates in the warmer half, travels through each sealed circuit and condenses in the cooler half before returning. An integral metal partition is expanded and sealed around every tube penetration so the two duct sections remain physically divided. Circuit geometry can be arranged for side-by-side horizontal air paths or one stream above the other, with the charge and return path selected for equal seasonal recovery or a preferred heating or cooling duty.
Características-chave
Copper tube penetrations are mechanically expanded into the integral divider to preserve separation between the two air paths.
Selections up to eight tube rows and multiple aluminum or copper fin densities match available face area and pressure-drop limits.
Accessible fin faces, protective coating options and a dedicated drain section simplify cleaning and wet-side maintenance.
Preocupações do produto do cliente
Heat-pipe recovery depends on the physical relationship between the two ducts, even airflow across the finned faces and suitable drainage and frost protection at the cold section.
Aplicações típicas
Parâmetros técnicos
Representative construction ranges for a divided HVAC heat-pipe recovery module are shown below.
| Material principal | Individually charged copper loop heat-pipe circuits with phase-change working fluid and aluminum fins |
|---|---|
| Painel de espessura | Approximately 230 mm finned core depth in the airflow direction for a typical six-row module |
| Largura efetiva | 500–3000 mm nominal finned-face width across common modular selections |
| Comprimento máximo | Up to 5080 mm active copper-tube length across the module face |
| Aço enfrentando espessura | Approximately 1.5 mm minimum galvanized or stainless frame and air-stream divider |
| Densidade Core | 8960 kg/m³ copper tube material |
| Condutividade térmica | Approximately 385 W/(m·K) for the copper tube wall |
| Superfície acabado | Aluminum fins on copper tubes with optional epoxy or hydrophilic coating and powder-coated casing |
| Tipo conjunto | Hermetically sealed loop circuits passing through an expanded tube-to-divider joint in a flanged frame |
| Customização | Disponível com base na aplicação pretendida e no ambiente operacional. |
Opções disponíveis
Planning a Heat-Pipe Energy Recovery Unit specification?
Envie-nos as suas dimensões, condições de instalação, metas de desempenho e acabamento de superfície necessário.

Inglês
Alemão
Língua árabe
Francês
Língua indonésia
Japonês
Coreano
Língua malaia
Portuguêsatual
Língua russa
Espanhol
Tailandês
Língua turca
Vietnã