열관 에너지 회수 장치
- Hermetically Sealed Copper Circuits
- Integral Air-Stream Divider
- Up to Eight Tube Rows
- Serviceable Finned Faces
상품 소개
The heat-pipe energy recovery unit extends individually charged copper circuits through two finned sections located in adjacent supply and exhaust ducts. Working fluid evaporates in the warmer half, travels through each sealed circuit and condenses in the cooler half before returning. An integral metal partition is expanded and sealed around every tube penetration so the two duct sections remain physically divided. Circuit geometry can be arranged for side-by-side horizontal air paths or one stream above the other, with the charge and return path selected for equal seasonal recovery or a preferred heating or cooling duty.
주요 기능
Copper tube penetrations are mechanically expanded into the integral divider to preserve separation between the two air paths.
Selections up to eight tube rows and multiple aluminum or copper fin densities match available face area and pressure-drop limits.
Accessible fin faces, protective coating options and a dedicated drain section simplify cleaning and wet-side maintenance.
고객 제품 관심사
Heat-pipe recovery depends on the physical relationship between the two ducts, even airflow across the finned faces and suitable drainage and frost protection at the cold section.
일반적인 응용 프로그램
기술 매개변수
Representative construction ranges for a divided HVAC heat-pipe recovery module are shown below.
| 핵심 재료 | Individually charged copper loop heat-pipe circuits with phase-change working fluid and aluminum fins |
|---|---|
| 패널 두께 | Approximately 230 mm finned core depth in the airflow direction for a typical six-row module |
| 유효 폭 | 500–3000 mm nominal finned-face width across common modular selections |
| 최대 길이 | Up to 5080 mm active copper-tube length across the module face |
| 강철 면면 두께 | Approximately 1.5 mm minimum galvanized or stainless frame and air-stream divider |
| 코어 밀도 | 8960 kg/m³ copper tube material |
| 열전도도 (Thermal Conductivity) | Approximately 385 W/(m·K) for the copper tube wall |
| 표면 마무리 | Aluminum fins on copper tubes with optional epoxy or hydrophilic coating and powder-coated casing |
| 접합 유형 | Hermetically sealed loop circuits passing through an expanded tube-to-divider joint in a flanged frame |
| 사용자 정의 | 의도된 응용 프로그램 및 운영 환경에 따라 사용할 수 있습니다. |