Unidade de manuseio de ar fresco
- 100% Outdoor Air Treatment
- Deep Cooling and Reheat
- Intake Filter Protection
- Cleanroom Pressurization Support
Introdução do produto
A fresh air handling unit treats the full outdoor-air load required for ventilation, process exhaust replacement and building pressurization. Its treatment train normally includes weather intake protection, staged filtration, cooling and dehumidifying coils, reheat and optional humidification. Because outdoor conditions vary widely, coils and valves are selected for peak latent as well as sensible duty. The supply fan modulates to the scheduled ventilation quantity while frost protection and drainable wet sections protect the unit during seasonal operation.
Características-chave
Deep cooling followed by controlled reheat separates moisture removal from final supply-air temperature.
Intake screens, dampers and prefilters protect coils from weatherborne debris and particulate loading.
Supply-air volume can track facility exhaust or pressure demand through variable-speed fan control.
Preocupações do produto do cliente
Outdoor air imposes the widest temperature, moisture and contamination range on a cleanroom HVAC system.
Aplicações típicas
Parâmetros técnicos
Typical casing construction for a cleanroom fresh-air handling unit is summarized below.
| Material principal | Closed-cell polyurethane insulation in weather-resistant double-skin panels |
|---|---|
| Painel de espessura | 50–70 mm insulated casing |
| Largura efetiva | 900–3200 mm nominal unit width |
| Comprimento máximo | Up to 10000 mm including intake, coil, filter and fan sections |
| Aço enfrentando espessura | 0.6–1.0 mm exterior and 0.8–1.0 mm wet-section lining |
| Densidade Core | 40–45 kg/m³ closed-cell polyurethane |
| Condutividade térmica | 0.022–0.026 W/(m·K) for polyurethane casing insulation |
| Superfície acabado | UV-stable powder-coated outer skin with galvanized or stainless cleanable inner skin |
| Tipo conjunto | Gasketed thermal-break frame with weather-sealed intake and modular section joints |
| Customização | Disponível com base na aplicação pretendida e no ambiente operacional. |
Opções disponíveis
Planning a Fresh Air Handling Unit specification?
Envie-nos as suas dimensões, condições de instalação, metas de desempenho e acabamento de superfície necessário.

Inglês
Alemão
Língua árabe
Francês
Língua indonésia
Japonês
Coreano
Língua malaia
Portuguêsatual
Língua russa
Espanhol
Tailandês
Língua turca
Vietnã