Seu fornecedor único para equipamentos de sala limpa e instalações assépticas essenciaisApoio Internacional a Projetos
Open mobile navigationClose mobile navigation
Equipamento de sala limpa Peças de reposição

FFU pré - filtro

A shallow coarse-media intake panel that captures fibers and large dust before they reach the FFU fan and final HEPA filter.
  • Low-Resistance Coarse Media
  • Shallow FFU Profile
  • Rigid Aluminum Frame
  • Easy Service Pull Tabs
Solicite um orçamento. Browse produtos

Introdução do produto

The FFU pre-filter installs at the fan intake to intercept lint, fibers and coarse particles before they load the impeller or final filter. A shallow aluminum frame holds synthetic media against an expanded-metal support grid, preserving open area under fan suction. Service tabs allow the panel to be removed from a restricted ceiling plenum without disturbing the HEPA filter. Face dimensions, thickness, media grade and airflow direction must match the FFU intake rack.

Características-chave

Open synthetic media adds limited resistance at normal FFU face velocity.

A rigid shallow frame remains square in the intake track during repeated service.

Expanded-metal support prevents media movement toward the rotating fan.

Pull tabs provide a defined grip point for overhead removal and replacement.

Preocupações do produto do cliente

An FFU intake filter must protect the fan without consuming the pressure reserve needed by the final filter.

Coarse debris accumulates on the impeller and changes fan balance.The upstream synthetic layer captures fibers and large particles before they enter the wheel.
A restrictive prefilter reduces airflow through the cleanroom HEPA filter.A shallow, open coarse-media structure preserves a broad effective flow area.
Unsupported media bows inward under fan suction.An expanded-metal grid stabilizes the media across the full panel face.
Flush panels are difficult to remove in a shallow ceiling plenum.Flexible pull tabs provide accessible service grips without adding significant depth.

Aplicações típicas

Cleanroom fan filter unit intakesLaminar-flow module prefiltrationMini-environment circulation unitsFFU fan and HEPA protection

Parâmetros técnicos

Typical construction ranges for FFU intake pre-filters are shown below.

Material principalBonded polyester or washable synthetic coarse-filter media with expanded-metal support
Painel de espessura10-30 mm nominal filter depth
Largura efetiva300-610 mm nominal face width
Comprimento máximoAté 1220 mm de comprimento nominal do rosto
Aço enfrentando espessura0.4-0.8 mm optional galvanized expanded-metal support grid
Densidade CoreApproximately 20-45 kg/m³ nominal synthetic-media bulk density
Condutividade térmicaApproximately 0.035-0.045 W/(m·K) for dry polyester media
Superfície acabadoNatural silver aluminum frame with clean white synthetic media and pull tabs
Tipo conjuntoMedia retained in a mitered shallow frame with bonded or mechanically fixed support grid
CustomizaçãoDisponível com base na aplicação pretendida e no ambiente operacional.

Opções disponíveis

Disposable or washable mediaCustom FFU face dimensionsUpstream or downstream support gridPull-tab location and quantity

Planning a FFU Pre-Filter specification?

Envie-nos as suas dimensões, condições de instalação, metas de desempenho e acabamento de superfície necessário.

Fale com a nossa equipe
Email-nos O WhatsApp WeChat

Início

Produtos

Notícias

Sobre nós

Contato