A thermally released curtain damper with spring-assisted closure for isolating a duct penetration while the ventilation system may still be moving air.
  • Spring-Driven Dynamic Closure
  • Interlocking Curtain Blades
  • Thermal Release Mechanism
  • Compact Sleeve Installation
Demander un devis. Browse les produits

Introduction de produit

The dynamic fire damper stores a folded stack of interlocking galvanized blades outside the normal airway. Under ordinary ventilation the curtain is held open by a thermal release. When released, stainless closure springs draw the blade stack across the opening and lock the interlocking folds into the guide channels. A factory sleeve and retaining-angle arrangement positions the damper at the wall or floor penetration while leaving access to the release and blade track for periodic inspection.

Key Features

Spring-assisted curtain travel supplies closing force even when air continues to move through the duct.

Interlocking galvanized blade folds form a continuous closure across the opening after release.

The open blade stack remains outside the clear airway to minimize normal pressure drop.

Sleeve, retaining-angle and access options adapt the damper to common wall and floor penetration details.

Préoccupations du client produit

A fire damper must be installed square at the protected penetration, retain unobstructed curtain travel and keep its thermal release accessible for inspection.

A static-only curtain may not close reliably against airflow from a fan that remains operating.Closure springs add force to pull the dynamic curtain through the moving airstream.
Mortar, fasteners or a distorted sleeve obstruct the blade guide channels.Specified clearance, protected tracks and square retaining angles preserve the curtain travel path.
The folded blade stack projects into the duct and creates unnecessary pressure loss.An out-of-airway curtain pocket keeps the open blades clear of the normal flow area.
The thermal link cannot be reached after the ceiling is closed.A coordinated access panel exposes the release, blade stack and track for visual and functional checks.

Les applications typiques

Cleanroom duct fire-compartment penetrationsHospital supply and return ductsLaboratory exhaust boundariesPharmaceutical facility shaftsCommercial HVAC wall and floor openings

Paramètres techniques

Representative construction ranges for a rectangular spring-assisted curtain fire damper are shown below.

Matériaux de baseInterlocking galvanized-steel curtain blades with stainless closure springs and thermal release
Panneau épaisseur0.7–1.0 mm formed interlocking curtain blade sheet
Largeur effective152–914 mm nominal single-section clear opening width
Longueur maximaleUp to 1219 mm nominal single-section opening height
Acier face épaisseur1.2–1.5 mm galvanized sleeve, frame and retaining components
Densité CoreApproximately 7850 kg/m³ for the steel curtain blades
Conductivité thermiqueApproximately 45–55 W/(m·K) for galvanized carbon steel
surface finieMill-galvanized curtain, sleeve and frame with corrosion-resistant spring hardware
Type jointSleeved penetration frame with spring-driven interlocking curtain, side tracks and thermal release
CustomisationDisponible en fonction de l'application prévue et de l'environnement d'exploitation.

Options disponibles

Vertical wall or horizontal floor orientationThermal release temperature selectionFactory sleeve and retaining anglesOpen-close indication switch