Su proveedor de ventanilla única para equipos de sala limpia y elementos esenciales para instalaciones asépticasApoyo a proyectos internacionales
Open mobile navigationClose mobile navigation
FFU y equipos de purificación de aire terminal

Unidad de filtro ULPA

A tightly sealed EC fan filter module configured with U15, U16 or U17 mini-pleat media for processes sensitive to ultrafine airborne particles.
  • U15-U17 Filter Options
  • Low-Leakage Gel Seal
  • Stable EC Airflow
  • Room-Side Service Option
Solicite un presupuesto. Browse productos

Introducción del producto

This ULPA fan filter unit combines an aluminium mini-pleat ULPA panel, a rigid powder-coated plenum and a backward-curved EC impeller in one ceiling module. A knife-edge gel seal isolates the downstream face from bypass leakage, while the internal pressure chamber distributes air evenly across the high-resistance filter. Individual 0-10 V control or network-ready regulation helps maintain the selected face velocity as filter resistance changes. It is intended for advanced microelectronics, nanotechnology and precision optical environments where an ordinary HEPA configuration may not provide the required particle-retention margin.

Características clave

U15-U17 mini-pleat media provides a higher particulate-retention level than a standard H14 module.

A gel-seal knife edge forms a continuous downstream barrier around the complete filter perimeter.

The EC impeller and pressure chamber maintain uniform discharge without a central high-velocity zone.

Room-side access can keep filter replacement and seal inspection within the controlled space.

Preocupaciones del producto del cliente

Ultrafine-particle control depends on both the ULPA media and the integrity of the complete fan, plenum and filter interface.

A high-efficiency filter can still allow bypass leakage around a compressed perimeter gasket.The knife-edge housing seats continuously in the gel channel to close the perimeter airflow path.
Dense ULPA media raises resistance and can reduce delivered face velocity as the filter loads.An EC fan with adjustable reserve pressure supports stable airflow through the higher-resistance filter pack.
Uneven plenum pressure creates local velocity peaks over sensitive wafers or optical components.Internal baffling spreads the fan discharge before it reaches the full ULPA filter face.
Removing a ceiling module from above can expose an ultraclean room during maintenance.A room-side replaceable arrangement allows the filter and sealing surface to be serviced from below.

Aplicaciones típicas

Semiconductor wafer fabricationAdvanced display manufacturingAsamblea óptica de precisiónNanotechnology research areasCritical mini-environments

Parámetros técnicos

Representative construction ranges for a ceiling-mounted ULPA fan filter unit are listed below.

Materiales CoreLow-boron micro-glass or membrane ULPA mini-pleat pack with aluminium separators and EC centrifugal fan
Panel de espesor330-450 mm overall module depth
Ancho efectivo575-1170 mm nominal ceiling-grid width
Longitud máximaUp to 1170 mm standard module length
Acero frente a espesor0.8-1.2 mm powder-coated steel housing; stainless-steel option available
Densidad CoreApproximately 90-120 kg/m³ compacted density of the ULPA filter pack
Conductividad térmicaApproximately 0.035-0.043 W/(m·K) for the high-efficiency micro-glass pack used in the ULPA FFU
Superficie acabadaWhite low-shedding powder coat with anodized aluminium or stainless perforated diffuser
Tipo conjuntoKnife-edge gel-seal filter interface with closed-cell ceiling perimeter gasket
CustomizationDisponible según la aplicación prevista y el entorno operativo.

Opciones disponibles

U15, U16 or U17 filter classDry gasket or gel-seal interface0-10 V, Modbus or grouped EC controlTop-side or room-side filter access

Planning a ULPA Fan Filter Unit specification?

Envíenos sus dimensiones, condiciones de instalación, objetivos de rendimiento y acabado superficial requerido.

Habla con nuestro equipo
E-mail Nos WhatsApp WeChat