상품 소개
Aluminum ductwork reduces the dead load carried by cleanroom ceiling supports while providing a naturally corrosion-resistant surface for conditioned air. Sections are fabricated from 3003 or 5052 aluminum sheet using lock-formed or welded seams and aluminum flange components. Because aluminum is softer than steel, panel reinforcement and support spacing are selected to prevent distortion during transport and operation. The non-sparking, non-ferrous construction is useful in selected technical areas, provided the conveyed chemicals and galvanic interfaces are compatible with the chosen alloy.
주요 기능
A stable aluminum oxide layer protects the surface in normal indoor clean-air service.
Non-ferrous construction avoids rust staining from exposed cut edges.
Formed stiffeners and closer hanger spacing control deformation in broad rectangular panels.
고객 제품 관심사
Lightweight aluminum duct must be detailed around its lower stiffness, dissimilar-metal contacts and the actual chemical exposure of the air stream.
일반적인 응용 프로그램
기술 매개변수
Common construction ranges for fabricated aluminum air duct are summarized below.
| 핵심 재료 | 3003-H14 or 5052-H32 aluminum alloy sheet |
|---|---|
| 패널 두께 | 0.8–1.8 mm, selected by duct dimension and pressure duty |
| 유효 폭 | 150–1600 mm rectangular side dimension |
| 최대 길이 | 1200–1500 mm per fabricated section |
| 강철 면면 두께 | 0.8–1.8 mm aluminum wall in place of steel facing |
| 코어 밀도 | Approximately 2700 kg/m³ solid aluminum construction |
| 열전도도 (Thermal Conductivity) | Approximately 138–170 W/(m·K), depending on aluminum alloy |
| 표면 마무리 | Mill finish, clear anodized or powder-coated aluminum |
| 접합 유형 | Aluminum flange or slip joint with compatible gasket and isolated fasteners |
| 사용자 정의 | 의도된 응용 프로그램 및 운영 환경에 따라 사용할 수 있습니다. |
사용 가능한 옵션
Planning a Aluminum Air Duct specification?
치수, 설치 조건, 성능 목표 및 필요한 표면 마감을 보내십시오.