Votre fournisseur à guichet unique pour les équipements de salle blanche et les essentiels des installations aseptiquesSoutien international aux projets
Open mobile navigationClose mobile navigation
Salle blanche HVAC et équipement de manutention de l'air

Unité d'air de maquillage

A dedicated outdoor-air unit that replaces exhausted process air and maintains the intended cleanroom pressure relationship.
  • Exhaust Air Replacement
  • Pressure Cascade Support
  • Tempered Outdoor Supply
  • Airflow Tracking Control
Demander un devis. Browse les produits

Introduction de produit

The makeup air unit delivers conditioned outside air in proportion to fume-hood, process, canopy or room exhaust. Unlike a general fresh-air unit, its primary control duty is mass-balance: supply airflow must respond predictably as exhaust devices start, stop or modulate. Filters, coils and optional humidity treatment bring the outdoor air to a condition that the room or recirculation system can accept without upsetting temperature and moisture control. A low-leakage casing and fast fan response help prevent door forces and unwanted infiltration.

Key Features

Supply airflow can track a combined exhaust-air signal rather than operate at one fixed ventilation rate.

Tempering coils prevent replacement air from imposing abrupt heating, cooling or moisture loads on the cleanroom.

Fast variable-speed fan control supports stable room pressure during process exhaust transitions.

Separate intake filtration prevents outdoor particles from entering through uncontrolled building leakage paths.

Préoccupations du client produit

A facility can have sufficient cooling capacity yet still lose pressure control when exhaust and replacement air do not change together.

Starting a process exhaust fan pulls adjacent cleanrooms below their pressure setpoint.The makeup fan follows the combined exhaust airflow signal with a configured offset for pressure cascade.
Untempered winter replacement air causes cold drafts and local condensation.Preheat and final heating stages deliver supply air at a controlled temperature.
Outdoor humidity overwhelms the room AHU during high exhaust operation.Cooling and dehumidification are sized for the full makeup-air latent load.
Unfiltered infiltration enters around doors when replacement air is insufficient.Measured makeup volume enters through staged filters and a defined supply path.

Les applications typiques

Pharmaceutical process exhaust replacementLaboratory fume-hood makeup airClean manufacturing canopy exhaustChemical handling roomsHospital isolation support areas

Paramètres techniques

Representative makeup-air unit casing and connection ranges are provided below.

Matériaux de baseClosed-cell polyurethane or mineral-wool insulation within double-wall casing
Panneau épaisseur50–60 mm insulated panel
Largeur effective800–3000 mm nominal casing width
Longueur maximaleUp to 9000 mm with staged filtration and thermal treatment
Acier face épaisseur0.6–1.0 mm sheet steel casing skins
Densité Core40–43 kg/m³ polyurethane or 80–96 kg/m³ mineral wool
Conductivité thermique0.022–0.040 W/(m·K) according to insulation selection
surface finiePowder-coated galvanized exterior with galvanized or stainless wet-section interior
Type jointThermal-break frame and gasketed block joints with flexible supply-duct connector
CustomisationDisponible en fonction de l'application prévue et de l'environnement d'exploitation.

Options disponibles

Exhaust-airflow or room-pressure trackingGas, steam, hot-water or electric heatingChilled-water, DX or desiccant dehumidificationOutdoor roof, floor or plant-room arrangement

Planning a Makeup Air Unit specification?

Envoyez-nous vos dimensions, conditions d'installation, objectifs de performance et finition de surface requise.

Parlez à notre équipe