Trang điểm Air Unit

A dedicated outdoor-air unit that replaces exhausted process air and maintains the intended cleanroom pressure relationship.
  • Exhaust Air Replacement
  • Pressure Cascade Support
  • Tempered Outdoor Supply
  • Airflow Tracking Control
Yêu cầu báo giá Duyệt các sản phẩm

Giới thiệu Sản phẩm

The makeup air unit delivers conditioned outside air in proportion to fume-hood, process, canopy or room exhaust. Unlike a general fresh-air unit, its primary control duty is mass-balance: supply airflow must respond predictably as exhaust devices start, stop or modulate. Filters, coils and optional humidity treatment bring the outdoor air to a condition that the room or recirculation system can accept without upsetting temperature and moisture control. A low-leakage casing and fast fan response help prevent door forces and unwanted infiltration.

Các tính năng chính

Supply airflow can track a combined exhaust-air signal rather than operate at one fixed ventilation rate.

Tempering coils prevent replacement air from imposing abrupt heating, cooling or moisture loads on the cleanroom.

Fast variable-speed fan control supports stable room pressure during process exhaust transitions.

Separate intake filtration prevents outdoor particles from entering through uncontrolled building leakage paths.

Các mối quan tâm về sản phẩm của khách hàng

A facility can have sufficient cooling capacity yet still lose pressure control when exhaust and replacement air do not change together.

Starting a process exhaust fan pulls adjacent cleanrooms below their pressure setpoint.The makeup fan follows the combined exhaust airflow signal with a configured offset for pressure cascade.
Untempered winter replacement air causes cold drafts and local condensation.Preheat and final heating stages deliver supply air at a controlled temperature.
Outdoor humidity overwhelms the room AHU during high exhaust operation.Cooling and dehumidification are sized for the full makeup-air latent load.
Unfiltered infiltration enters around doors when replacement air is insufficient.Measured makeup volume enters through staged filters and a defined supply path.

Các ứng dụng điển hình

Pharmaceutical process exhaust replacementLaboratory fume-hood makeup airClean manufacturing canopy exhaustChemical handling roomsHospital isolation support areas

Thông số kỹ thuật

Representative makeup-air unit casing and connection ranges are provided below.

Vật liệu lõiClosed-cell polyurethane or mineral-wool insulation within double-wall casing
Độ dày bảng điều khiển50–60 mm insulated panel
Chiều rộng hiệu quả800–3000 mm nominal casing width
Chiều dài tối đaUp to 9000 mm with staged filtration and thermal treatment
Thép đối mặt với độ dày0.6–1.0 mm sheet steel casing skins
Mật độ lõi40–43 kg/m³ polyurethane or 80–96 kg/m³ mineral wool
Độ dẫn nhiệt0.022–0.040 W/(m·K) according to insulation selection
Kết thúc bề mặtPowder-coated galvanized exterior with galvanized or stainless wet-section interior
Loại khớp nốiThermal-break frame and gasketed block joints with flexible supply-duct connector
Tùy chỉnhCó sẵn dựa trên ứng dụng dự định và môi trường hoạt động.

Các tùy chọn có sẵn

Exhaust-airflow or room-pressure trackingGas, steam, hot-water or electric heatingChilled-water, DX or desiccant dehumidificationOutdoor roof, floor or plant-room arrangement