موردك الموحد لمعدات الغرف النظيفة وأساسيات المرافق العقليةدعم المشاريع الدولية
Open mobile navigationClose mobile navigation
أنظمة توزيع الهواء في الغرف النظيفة

قناة الهواء الفينولية معزولة مسبقًا

A rigid aluminum-faced phenolic foam duct system that combines a low-conductivity insulation core, vapor barrier and air passage in one lightweight panel assembly.
  • Low-Conductivity Phenolic Core
  • Continuous Foil Vapor Barrier
  • Lightweight Rigid Construction
  • Compact Insulated Wall
طلب عرض أسعار تصفح المنتجات

مقدمة المنتج

Phenolic pre-insulated ductwork is fabricated from rigid closed-cell phenolic foam panels laminated with aluminum foil on both faces. The relatively low thermal conductivity provides useful insulation in a thin wall, leaving more service space around the finished duct. Sections are produced by grooving, folding and sealing the panel, then connected using aluminum or polymer profiles with foil tape and vapor-compatible sealant. The system is intended for dry HVAC air distribution and benefits projects that need low installed mass and a clean external finish.

الخصائص الرئيسية

Closed-cell phenolic foam limits heat transfer and moisture migration through a compact panel thickness.

Aluminum foil laminates protect both panel faces and form the visible air and vapor barriers.

Low panel mass simplifies lifting through congested plant rooms and above cleanroom ceilings.

Purpose-made connection profiles protect foam edges and transfer loads across section joints.

مخاوف المنتج للعملاء

Phenolic duct performance depends on preserving the foil skins and sealing every groove, corner and transverse connection without crushing the foam core.

Limited ceiling depth leaves little room for bulky external duct insulation.A thin phenolic wall integrates insulation directly into the duct envelope.
Unprotected foam edges release particles during handling.Edge channels, foil tape and sealant enclose every cut face before installation.
Vapor leakage at panel corners produces hidden condensation.Continuous external foil tape bridges the corner and connects the facing into one vapor barrier.
Point loads from hangers crush the lightweight panel.Wide support saddles distribute the duct weight across reinforced outer surfaces.

تطبيقات نموذجية

Cleanroom supply-air distributionConditioned return-air branchesHealthcare ventilationCommercial laboratory HVACLightweight modular plant rooms

المعلمات الفنية

Typical data for aluminum-faced phenolic pre-insulated duct panels are presented below.

المواد الأساسيةClosed-cell rigid phenolic foam
سمك اللوحة22–30 mm
العرض الفعال1200 mm standard panel width
الحد الأقصى الطول2950–3930 mm standard panel length
الصلب يواجه سمك0.04–0.20 mm aluminum foil laminate on each face
الكثافة الأساسية55–60 kg/m³
الموصلية الحراريةApproximately 0.022 W/(m·K) at 10°C mean temperature
إنهاء السطحEmbossed aluminum foil on both internal and external faces
نوع المشتركProfiled panel connection sealed with compatible adhesive, foil tape and vapor sealant
التخصيصمتوفر على أساس التطبيق المقصود وبيئة التشغيل.

الخيارات المتاحة

22 mm or 30 mm panel thicknessReinforced aluminum outer skinFlanged terminal and equipment adaptersFactory-cut elbows, reducers and branches