Gas نظام إغلاق الطوارئ
- Automatic or manual isolation of selected gas sources
- Normally closed pneumatic valve removes flow when pilot pressure is vented
- Separate input, output, alarm and reset status at the controller
مقدمة المنتج
The Gas Emergency Shut-Off System combines a wall-mounted safety controller with one or more high-purity pneumatic isolation valves. During normal operation, controlled pilot pressure holds each normally closed diaphragm valve open. A mapped gas detector, fire contact, process permissive or emergency-stop input causes the controller to vent that pilot pressure and isolate the corresponding gas source. Local status indication, an audible alarm, dry contacts and optional network access help operators identify the initiating channel without turning the shut-off assembly into the gas detector itself. The gas service, valve materials, cause-and-effect logic, reset method and proof-test interval are selected for the actual hazard and delivery system.
الخصائص الرئيسية
Pneumatic fail-closed valve architecture converts loss of pilot pressure into a closed gas path
A prominent local mushroom button provides direct manual shutdown without navigating a display menu
Independent channel indicators show input and valve-command states for faster incident interpretation
Master and channel relay contacts can pass alarm, shutdown and fault information to a building or process system
A high-purity diaphragm valve with metal-to-metal body sealing limits added contamination in compatible gas service
Separate process and pilot connections keep hazardous gas out of the controller enclosure
Latched shutdown and deliberate reset options reduce unintended reopening after an alarm condition clears
Event and remote-status options support review of trips, resets and loss-of-utility conditions
Single- or multi-source arrangements can be configured without changing the basic fail-closed isolation principle
مخاوف المنتج للعملاء
Effective emergency isolation depends on the complete cause-and-effect chain: the initiating contact, controller logic, pilot utility, shut-off valve and downstream trapped volume all need to behave as intended under fault conditions.
تطبيقات نموذجية
المعلمات الفنية
The displayed product basis is a compact controller-and-single-valve assembly using a flame-retardant polycarbonate control enclosure, a separate 316L stainless steel normally closed pneumatic diaphragm valve and a brushed stainless mounting plate. The controller envelope is represented at approximately 363 mm high, 324 mm wide and 210 mm deep before the external valve and service clearances are added. The site's fixed ten-row schema uses panel-oriented labels; Steel Facing Thickness therefore distinguishes the molded enclosure from the separate mounting plate. Channel count, input logic, valve port size, pilot pressure and communication arrangement remain application-selected.
| المواد الأساسية | Flame-retardant polycarbonate controller enclosure with internal control electronics, paired with a 316L stainless steel normally closed pneumatic diaphragm valve and separate stainless mounting plate |
|---|---|
| سمك اللوحة | 210 mm nominal controller depth for the selected catalogue basis, excluding the external valve and service clearance |
| العرض الفعال | 324 mm nominal controller width for the selected catalogue basis |
| الحد الأقصى الطول | 363 mm nominal controller height, excluding pneumatic tubing, valve assembly and cable entries |
| الصلب يواجه سمك | 0 mm steel facing on the molded controller enclosure; a separate approximately 2.0 mm stainless mounting plate may be supplied |
| الكثافة الأساسية | Approximately 1200 kg/m³ representative density for the unfilled polycarbonate enclosure material |
| الموصلية الحرارية | Approximately 0.20 W/(m·K) near 23°C for representative unfilled polycarbonate |
| إنهاء السطح | Warm light-gray molded polymer enclosure, charcoal status panel, red/yellow emergency control, natural-silver stainless valve and backplate, and restrained multicolor status lenses |
| نوع المشترك | Normally closed pneumatic diaphragm valve with opposed threaded or face-seal process ports, separate pilot port, controller bulkhead connections and terminal or network interfaces |
| التخصيص | متوفر على أساس التطبيق المقصود وبيئة التشغيل. |
الخيارات المتاحة
Planning a Gas Emergency Shut-Off System specification?
أرسل لنا الأبعاد الخاصة بك، شروط التثبيت، أهداف الأداء والتشطيب السطحي المطلوب.

English
الألمانية
العربيةالحالي
الفرنسية
الإندونيسية
اليابانية
الكورية
اللغة الملاوية
البرتغالية
الروسية
الإسبانية
التايلاندية
اللغة التركية
اللغة الفيتنامية