Su proveedor de ventanilla única para equipos de sala limpia y elementos esenciales para instalaciones asépticasApoyo a proyectos internacionales
Open mobile navigationClose mobile navigation
Accesorios de instalación de sala limpia

Puerto de prueba de presión ambiente

A flush brushed-stainless wall port that provides a capped connection point for cleanroom differential-pressure verification and reference tubing.
  • Flush Stainless Wall Plate
  • Capped M5 Test Nipple
  • Two-Screw Mounting Pattern
  • Rear Pressure-Tube Connection
Solicite un presupuesto. Browse productos

Introducción del producto

The room pressure test port uses a slim rectangular stainless faceplate to bring a low-pressure reference line to an accessible cleanroom wall surface. A central threaded service nipple accepts a compatible portable manometer hose, while the rear fitting connects to the concealed pressure tube. The knurled closure stays attached to a dedicated chain anchor and seals the exposed test point between checks. Two vertically aligned mounting holes and a compressible backing gasket keep the plate stable and limit false readings caused by air movement from the wall cavity.

Características clave

The low-profile brushed plate presents a smooth wipeable surface at the monitored room boundary.

A central M5 service nipple gives technicians a defined connection for compatible differential-pressure test tubing.

The knurled sealing cap closes the pressure opening between measurements and remains captured by a short stainless chain.

Two countersunk holes on the vertical centerline secure the plate without crowding the pressure fitting.

A single rear bulkhead connector provides a direct transition to the concealed reference tube without an exposed instrument body.

Preocupaciones del producto del cliente

Very small room pressure differences are easily distorted by wall-cavity drafts, contaminated tubing or an unsealed service connection.

Air leaking around a loose wall plate can bias the pressure reference at the pickup point.The two-screw faceplate compresses a compatible backing gasket against the finished wall surface.
An open test nipple can collect cleaning residue or become a persistent pressure leak.The close-fitting knurled cap seals the front connection and stays attached to its dedicated chain anchor.
Long, kinked or wet reference tubing slows response and produces unstable manometer readings.The direct rear fitting supports a short, correctly routed tube that can be inspected for blockage and condensation.
A service fitting mounted without anti-rotation support can loosen when test hoses are connected repeatedly.The rectangular plate and separated top-and-bottom fixings resist turning loads around the central nipple.

Aplicaciones típicas

Portable verification of cleanroom-to-corridor pressure differenceReference pressure pickup at isolation and protection roomsCommissioning checks for cleanroom pressure cascadesService access for remote differential-pressure transmitter tubingRoutine maintenance checks in laboratories and controlled production suites

Parámetros técnicos

Typical construction and dimensional ranges for a stainless cleanroom wall pressure test port are listed below.

Materiales Core316L stainless-steel faceplate, pressure nipple, cap and chain with a stainless or nickel-plated rear tube fitting
Panel de espesor25-120 mm compatible modular wall or ceiling panel thickness
Ancho efectivoApproximately 70 mm nominal single-gang faceplate width
Longitud máximaUp to 120 mm overall faceplate length
Acero frente a espesor1.0-1.5 mm nominal stainless faceplate thickness
Densidad CoreApproximately 7900-8000 kg/m³ for austenitic stainless-steel components
Conductividad térmicaApproximately 14-16 W/(m·K) for 316L stainless steel
Superficie acabadaFine-brushed and passivated natural stainless steel with smooth radiused plate edges
Tipo conjuntoTwo-screw gasketed wall plate with central M5 front test nipple and coaxial rear pressure-tube connection
CustomizationDisponible según la aplicación prevista y el entorno operativo.

Opciones disponibles

304 or 316L stainless-steel plate and hardwareAlternative front test-thread and hose-adapter sizesBarbed or positive-lock rear tubing connectionPanel-depth gland extension for thicker cleanroom wallsEPDM or silicone backing gasket and custom fixing-hole spacing