A capacitive relative-humidity sensor that measures cleanroom moisture with a protected sensing element and serviceable wall or duct housing.
  • Capacitive RH Measurement
  • Replaceable Sensor Filter
  • Low-Drift Signal Conditioning
  • Wall or Duct Format
Solicite un presupuesto. Browse productos

Introducción del producto

The cleanroom humidity sensor uses a capacitive polymer element whose electrical response changes with water-vapor concentration. A protective membrane or porous filter shields the element from particles and incidental contact while allowing moisture diffusion. Signal conditioning linearizes and temperature-compensates the RH output for connection to environmental monitoring or HVAC controls. Wall versions use a compact ventilated enclosure; duct versions place a filtered probe into the airstream while keeping wiring accessible outside the duct.

Características clave

Capacitive sensing responds across normal cleanroom humidity ranges without a moving mechanism.

A replaceable filter protects the sensitive element from dust and handling contamination.

Temperature compensation reduces humidity error caused by normal room-temperature variation.

Wall and duct formats place the same sensing principle at the appropriate measurement location.

Preocupaciones del producto del cliente

Humidity measurement is vulnerable to contamination, local condensation and unsuitable mounting locations that do not represent the room air.

Cleaning residue coats the humidity element and causes slow drift.A replaceable protective filter reduces direct contamination and simplifies service.
Condensation temporarily saturates the sensor after a cold-air event.A hydrophobic filter and appropriate probe placement reduce liquid-water contact.
A wall pocket measures stagnant air rather than the occupied zone.Ventilated housing and considered mounting height expose the element to representative circulation.
Long field wiring adds noise to a low-level sensor signal.Integrated active signal conditioning provides a robust current, voltage or digital output.

Aplicaciones típicas

Cleanroom relative humidity monitoringAHU supply-air measurementStability roomsElectronics humidity control

Parámetros técnicos

Typical materials and dimensions for a cleanroom capacitive humidity sensor are listed below.

Materiales CoreCapacitive polymer RH element with hydrophobic membrane in polycarbonate wall or probe housing
Panel de espesor25-45 mm wall-sensor depth
Ancho efectivo80-120 mm wall housing width
Longitud máximaDuct probes up to 300 mm
Acero frente a espesor0-0.8 mm; optional stainless probe tube
Densidad Core1180-1220 kg/m³ for polycarbonate housing
Conductividad térmica0.19-0.22 W/(m·K) for polycarbonate enclosure material
Superficie acabadaSmooth white wall housing or satin stainless probe with white electronics head
Tipo conjuntoSnap-fit wall enclosure or threaded duct flange with replaceable filtered sensor cap
CustomizationDisponible según la aplicación prevista y el entorno operativo.

Opciones disponibles

Wall or duct probeVoltage, current or digital outputReplaceable membrane filterRemote probe cable