An actuated multiblade assembly that restricts smoke leakage during control sequences and closes the protected duct opening when its thermal release operates.
  • Dual Fire and Smoke Function
  • Sealed Airfoil Blade Bank
  • Spring-Return Safety Actuator
  • Open-Close Position Feedback
見積もりリクエスト 製品案内

商品紹介

The combination fire and smoke damper integrates a sealed multiblade smoke-control assembly with a thermally responsive closure device in one sleeved penetration unit. During normal operation the external actuator can open, close or modulate the airfoil blades for system sequences. A smoke-control command drives the spring-return actuator toward its safety position, while the thermal release provides an independent response to elevated temperature. Blade and jamb seals restrict leakage, and end switches can report the fully open and fully closed positions.

主要な特徴

One sleeved assembly performs both duct-penetration fire closure and powered smoke isolation functions.

Airfoil blades reduce operating pressure drop while edge and jamb seals improve closed-position smoke control.

A spring-return actuator drives the selected safety position when control power is removed.

Thermal release and optional position switches support independent closure response and remote status monitoring.

お客様の製品に関する懸念事項

Combined protection depends on correct installation at the rated opening, adequate actuator torque, intact blade seals and a control sequence that distinguishes smoke response from normal HVAC operation.

Separate fire and smoke dampers require extra duct length and two access locations.A single combination assembly consolidates thermal closure, sealed blades and actuation at one penetration.
A weak actuator cannot close the blade bank against fan pressure and seal friction.The spring-return torque is selected from damper area, blade arrangement and maximum differential pressure.
Operators cannot tell whether the damper reached its commanded safety position.Blade-linked open and closed switches provide status independent of the controller command signal.
Seal damage goes unnoticed because only actuator movement is tested.Periodic access to the blade edges and jambs allows the mechanical closure and compressible seals to be inspected together.

典型的な用途

Cleanroom fire and smoke compartment boundariesHospital smoke-control zonesLaboratory supply and exhaust penetrationsPharmaceutical production corridorsHigh-rise HVAC shafts and floors

技術的なパラメータ

Typical mechanical construction ranges for a rectangular combination fire and smoke damper are listed below.

コア材料Galvanized-steel airfoil blades with silicone or TPE smoke seals, steel shafts and thermal release
パネルの厚さ1.2–1.5 mm fabricated airfoil blade skins and frame components
有効幅152–1219 mm nominal single-section opening width
最大長さUp to 1880 mm nominal single-section opening height
鋼鉄の厚さを直面する1.2–1.5 mm galvanized sleeve and damper frame
コア密度Approximately 7850 kg/m³ for galvanized steel blades and frame
熱伝導率Approximately 45–55 W/(m·K) for carbon-steel airflow components
表面仕上げMill-galvanized blade, frame and sleeve with heat-resistant seals and protected actuator bracket
ジョイントタイプSleeved flanged frame with linked sealed blades, spring-return actuator and thermal closure device
カスタマイズ意図したアプリケーションと動作環境に基づいて利用できます。

利用可能なオプション

1.5-hour or 3-hour construction family24 V, 120 V or 230 V spring-return actuatorAuxiliary open-close indicationGalvanized, 304 or 316 stainless-steel airflow components

Planning a Combination Fire and Smoke Damper specification?

寸法、設置条件、性能目標、必要な表面仕上げをお送りください。

チームに相談する