Su proveedor de ventanilla única para equipos de sala limpia y elementos esenciales para instalaciones asépticasApoyo a proyectos internacionales
Open mobile navigationClose mobile navigation
Inicio / Productos / Equipos de sala limpia específicos de la industria / Operating Room Laminar Flow Ceiling
Equipos de sala limpia específicos de la industria

Sala de operaciones Laminar Flow Ceiling

A rectangular surgical ceiling canopy that distributes conditioned air through six terminal HEPA modules and perforated diffusers over the operating zone.
  • Six-Module HEPA Array
  • Unidirectional Downflow Face
  • Room-Side Filter Service
  • Integrated Linear Lighting
Solicite un presupuesto. Browse productos

Introducción del producto

The operating room laminar flow ceiling combines a shallow sealed supply plenum, six terminal HEPA modules and a planar perforated diffuser face in one suspended canopy. Conditioned air enters through the centered top collar, equalizes inside the pressure chamber and passes vertically through the filter array. Powder-coated steel casing, anodized aluminum filter rails, gasketed room-side retainers and two recessed light strips form a coordinated ceiling terminal with accessible service points and cleanable exposed surfaces.

Características clave

Six separately retained HEPA modules create a broad filtered-air face without relying on one oversized disposable element.

Perforated diffuser panels add resistance after the filters to reduce local jets and improve distribution across the canopy face.

Room-side latches and continuous gaskets allow individual filter access while maintaining a defined sealing interface.

Two recessed linear luminaires sit outside the active filter grid so task lighting does not divide the central airflow area.

Preocupaciones del producto del cliente

A surgical canopy must deliver a broad, stable filtered-air zone while preserving service access and coordinating ceiling-mounted lighting and ventilation interfaces.

Uneven plenum pressure can produce fast local jets and weak areas across the operating zone.A common pressure chamber and matched perforated diffuser faces distribute supply air across all six terminal modules.
Replacing a terminal filter from above can disrupt ceiling services and extend maintenance access time.Room-side locking frames release one gasketed module at a time without dismantling the complete canopy.
Leak paths around filter frames can bypass the intended terminal filtration route.Continuous compression gaskets, rigid aluminum rails and quarter-turn retainers form a controlled perimeter seal.
Separate light fittings can interrupt the filtered ceiling face or create difficult ceiling junctions.Twin recessed linear lights are integrated along the outer rails while the six-module central grid remains continuous.

Aplicaciones típicas

Orthopedic and implant operating theatresGeneral surgical operating roomsHybrid and image-guided procedure suitesSterile instrument preparation areas

Parámetros técnicos

Typical configurable construction values for a rectangular operating-room laminar airflow ceiling are listed below.

Materiales CoreEpoxy powder-coated galvanized steel plenum with anodized EN AW-6063 aluminum frames, H14 HEPA modules and perforated diffusers
Panel de espesor400-450 mm overall plenum depth
Ancho efectivo1880-2480 mm nominal diffuser width
Longitud máximaUp to 3080 mm standard canopy length
Acero frente a espesor1.0-1.2 mm powder-coated galvanized or optional stainless plenum sheet
Densidad Core2700 kg/m³ for anodized EN AW-6063 aluminum frame components
Conductividad térmica200-220 W/(m·K) for EN AW-6063 aluminum framing at room temperature
Superficie acabadaRAL 9010 epoxy powder-coated housing with satin anodized aluminum rails and white perforated diffuser faces
Tipo conjuntoGasketed room-side filter locking frames within a modular perimeter, sealed top plenum and flanged rectangular inlet
CustomizationDisponible según la aplicación prevista y el entorno operativo.

Opciones disponibles

Standard and custom rectangular canopy dimensionsPowder-coated galvanized or stainless steel plenum constructionFour-, six- or eight-module terminal filter arrangementsIntegrated linear lighting or sealed surgical-light passage

Planning a Operating Room Laminar Flow Ceiling specification?

Envíenos sus dimensiones, condiciones de instalación, objetivos de rendimiento y acabado superficial requerido.

Habla con nuestro equipo
E-mail Nos WhatsApp WeChat

Inicio

Productos

Noticias

Nosotros

Contacto