Su proveedor de ventanilla única para equipos de sala limpia y elementos esenciales para instalaciones asépticasApoyo a proyectos internacionales
Open mobile navigationClose mobile navigation
Inicio / Productos / Filtro de aire y filtración química / High-Airflow Medium-Efficiency Filter
Filtro de aire y filtración química

Filtro de alta eficiencia de flujo de aire

A reinforced extended-surface filter built to process higher air volumes while maintaining open channels through a deep supported media pack.
  • High Face Velocity
  • Reinforced Metal Cell
  • Open Deep-Pleat Channels
  • Large Dust Storage
Solicite un presupuesto. Browse productos

Introducción del producto

The high-airflow medium-efficiency filter combines a deep extended-surface media pack with rigid galvanized or aluminized-steel cell sides, protective faceguards and structural support straps. Corrugated separators or stabilized pleat spacers maintain open channels through the full depth of the pack as face velocity rises. A high-loft microglass or synthetic medium stores particles through its depth, while the rigid header resists the pulsation and turbulence found in large air handlers and process-air inlets. This construction emphasizes mechanical stability and airflow capacity rather than minimum cabinet depth.

Características clave

A deep pack exposes enough media area for elevated airflow without excessive local media velocity.

Corrugated separators preserve full-length channels under turbulent inlet conditions.

Metal faceguards and cross straps protect the pack from bowing and handling damage.

A high-strength enclosing cell keeps the gasket plane flat under sustained differential pressure.

Preocupaciones del producto del cliente

High-volume systems expose filter packs to turbulence, pulsation and structural loads that ordinary medium filters may not withstand.

Increasing airflow sharply raises pressure drop through a small media pack.A full-depth extended-surface pack lowers velocity at the media and preserves open flow channels.
Turbulent inlet air bows the pleats and damages the pack perimeter.Corrugated separators, faceguards and support straps share the load across the rigid cell.
Repeated fan starts loosen the internal pack-to-frame bond.Deep polyurethane potting anchors the entire media perimeter inside the metal cell.
A distorted header leaves compression gaps along the filter bank.Reinforced galvanized cell sides maintain a flat gasket surface at high operating pressure.

Aplicaciones típicas

Large central air-handling unitsCleanroom make-up-air plantsProcess ventilation systemsIndustrial supply-air filtrationHigh-volume turbine and compressor intake prefiltration

Parámetros técnicos

Typical construction ranges for a reinforced high-airflow medium-efficiency filter are listed below.

Materiales CoreHigh-loft microglass or synthetic media with corrugated aluminum or hot-melt separators
Panel de espesor292 mm nominal extended-surface depth
Ancho efectivo305-610 mm modular face width
Longitud máximaUp to 610 mm standard face length
Acero frente a espesor0.80-1.20 mm galvanized or aluminized-steel cell sides and faceguards
Densidad CoreApproximately 80-135 kg/m³ nominal supported media-pack density
Conductividad térmicaApproximately 0.034-0.043 W/(m·K) for the dry filter medium
Superficie acabadaMill-galvanized or aluminized-steel cell with white media and metallic faceguards
Tipo conjuntoDeep pleated pack potted into a reinforced rigid cell with single or double header
CustomizationDisponible según la aplicación prevista y el entorno operativo.

Opciones disponibles

MERV 11 or MERV 14 mediaStandard- or high-capacity pleat packSingle-header or double-header cellUpstream prefilter clips and heavy-duty faceguards

Planning a High-Airflow Medium-Efficiency Filter specification?

Envíenos sus dimensiones, condiciones de instalación, objetivos de rendimiento y acabado superficial requerido.

Habla con nuestro equipo
E-mail Nos WhatsApp WeChat

Inicio

Productos

Noticias

Nosotros

Contacto