Unité d'air de recirculation de la salle blanche (RCU)
- Return-Air Recirculation
- Optional Cooling Coil
- EC Volume Control
- Integrated Prefilter and HEPA
Introduction de produit
The cleanroom recirculation air unit draws room return air through a washable prefilter, passes it across an optional chilled-water coil and drives it through a HEPA or ULPA final filter. Fan, coil, condensate tray and controls are contained in a serviceable vertical cabinet, reducing the duct length required for a local clean zone. Temperature sensors can modulate the coil valve independently of EC fan speed so thermal load and cleanliness airflow are addressed separately. Supply may discharge through a front diffuser or connect to a short ceiling plenum serving adjacent work areas.
Key Features
The optional chilled-water coil removes local sensible heat without sending all recirculated air back to a remote AHU.
Separate EC fan and valve control allows airflow volume and temperature response to be tuned independently.
A sloped stainless condensate tray provides a defined drainage path beneath the cooling section.
Préoccupations du client produit
High recirculation rates and concentrated equipment heat can overload distant ductwork even when the central make-up air system is correctly sized.
Les applications typiques
Paramètres techniques
Typical enclosure and filtration ranges for a local cleanroom recirculation unit are listed below.
| Matériaux de base | EC centrifugal fan, optional copper-aluminium cooling coil, washable prefilter and micro-glass HEPA or ULPA pack |
|---|---|
| Panneau épaisseur | 550-900 mm cabinet depth |
| Largeur effective | 700-1400 mm serviceable cabinet width |
| Longueur maximale | Up to 2400 mm overall vertical cabinet height |
| Acier face épaisseur | 1.0-1.5 mm powder-coated steel casing with 1.0-1.5 mm stainless wet-section liner |
| Densité Core | Approximately 40-60 kg/m³ density for the closed-cell cabinet insulation |
| Conductivité thermique | Approximately 0.022-0.030 W/(m·K) for the closed-cell thermal insulation |
| surface finie | White low-shedding powder coat with stainless-steel coil and condensate compartment |
| Type joint | Gasketed double-skin service doors with flanged supply outlet and trapped condensate-drain connection |
| Customisation | Disponible en fonction de l'application prévue et de l'environnement d'exploitation. |
Options disponibles
Planning a Cleanroom Recirculation Air Unit (RCU) specification?
Envoyez-nous vos dimensions, conditions d'installation, objectifs de performance et finition de surface requise.