A targeted gas-phase filter loaded with acid-impregnated pellets that convert ammonia into a retained, non-volatile form within the media bed.
  • NH3-Targeted Chemistry
  • Low-Dust Pellets
  • Uniform Packed Bed
  • Laboratory Air Control
견적 요청 제품 찾아보기

상품 소개

The ammonia removal filter uses porous carbon or alumina carrying an acidic impregnant chosen to neutralize NH3. The media is contained in a corrosion-resistant box or refillable cartridge with a uniform depth across the airflow path. This dedicated chemistry provides more reliable ammonia capacity than untreated carbon and helps protect staff areas, animals, process materials and downstream HVAC components. A particle prefilter should be installed upstream to keep the reactive surface accessible.

주요 기능

Acid-impregnated granules chemically retain ammonia instead of relying only on weak physical adsorption.

Even media packing supports consistent residence time across the entire face.

Corrosion-resistant mesh and casing tolerate the intended basic-gas environment.

Serviceable cell formats simplify staged replacement after media-capacity monitoring.

고객 제품 관심사

Ammonia has a low molecular weight and weak affinity for untreated carbon, so a general odour filter may fail without warning.

Untreated carbon releases ammonia again as conditions change.Acid impregnation converts captured NH3 into a more strongly retained salt.
Odour is noticed before a planned maintenance interval ends.A deeper bed and scheduled media-capacity checks provide a more predictable replacement point.
Filter housing components corrode in a persistent ammonia atmosphere.Stainless steel or coated metal construction isolates the media and resists surface attack.
Adsorbent fines escape from a vibrating air-handling unit.Fine outlet screens and compressed media retain pellets and dust inside the cartridge.

일반적인 응용 프로그램

Animal holding roomsChemical analysis laboratoriesFertilizer production support areasAmmonia refrigeration plant roomsWastewater treatment ventilation

기술 매개변수

Representative material and size ranges for an ammonia-specific gas filter are shown below.

핵심 재료Acid-impregnated activated carbon or activated alumina formulated for NH3 capture
패널 두께100–292 mm overall cartridge or box-cell depth
유효 폭145–610 mm nominal module width
최대 길이Up to 610 mm nominal module height
강철 면면 두께0.8–1.2 mm galvanized, coated or 304 stainless steel
코어 밀도500–700 kg/m³ packed selective-media bulk density
열전도도 (Thermal Conductivity)0.10–0.22 W/(m·K) for the packed reactive media
표면 마무리Brushed stainless steel or chemical-resistant white powder coat
접합 유형Sealed cassette with retained pellet bed and continuous perimeter gasket
사용자 정의의도된 응용 프로그램 및 운영 환경에 따라 사용할 수 있습니다.

사용 가능한 옵션

Box cell or cylindrical canisterAcid-treated carbon or aluminaStainless-steel constructionLow-dust downstream scrim