Votre fournisseur à guichet unique pour les équipements de salle blanche et les essentiels des installations aseptiquesSoutien international aux projets
Open mobile navigationClose mobile navigation
Filtres à air et filtration chimique

Filtre à air moléculaire VOC

A high-capacity activated-carbon cell designed to adsorb volatile organic compounds and solvent vapours from process, make-up or recirculated air.
  • High-Surface-Area Carbon
  • VOC Adsorption
  • Low Bypass Construction
  • Replaceable Media Cell
Demander un devis. Browse les produits

Introduction de produit

This VOC filter contains virgin coconut-shell or coal-based activated carbon selected for non-polar organic vapours. The adsorbent is packed into a rigid V-bank or box cell to combine a large media mass with practical airflow. Internal screens and seals eliminate edge bypass and limit carbon fines. It is commonly preceded by particulate filtration so dust does not block the carbon pores, and it may be followed by a final filter where product cleanliness is critical.

Key Features

Microporous activated carbon provides a broad adsorption surface for many organic vapours.

A deep or V-bank bed carries substantially more adsorbent than a thin carbon pad.

Internal media screens reduce carbon migration into the downstream system.

Gasketed frame interfaces suit front- or side-access filter housings.

Préoccupations du client produit

Low-boiling solvents and process VOCs pass through particle filters and may contaminate products or create persistent odour.

A carbon-coated pad saturates quickly during routine solvent use.A deep bed increases usable carbon mass and extends the adsorption interval.
High humidity occupies adsorption sites and shortens filter life.Media grade and airflow residence time are selected for the expected humidity and VOC family.
Dust loads the carbon surface before it can adsorb vapour.An upstream fine-particle stage protects pores and preserves molecular capacity.
Unsealed filter edges let untreated air bypass the media bed.Continuous gaskets and bonded internal joints close the frame-to-housing path.

Les applications typiques

Solvent-handling cleanroomsPrinting and coating areasLaboratory recirculation airElectronics production make-up airOdour control in occupied technical spaces

Paramètres techniques

Common construction ranges for a deep-bed VOC molecular filter are listed below.

Matériaux de baseVirgin activated carbon selected for hydrocarbons, solvents and broad-spectrum VOC adsorption
Panneau épaisseur150–292 mm overall filter depth
Largeur effective305 - 610 mm Largeur nominale du visage
Longueur maximaleUp to 762 mm nominal face height
Acier face épaisseur0.7–1.2 mm galvanized or stainless-steel frame and retainers
Densité Core420–560 kg/m³ packed activated-carbon bulk density
Conductivité thermique0.09–0.18 W/(m·K) for packed activated carbon
surface finieGalvanized steel, brushed stainless steel or low-emission powder coat
Type jointSealed deep-bed or V-bank cell with continuous polyurethane or neoprene gasket
CustomisationDisponible en fonction de l'application prévue et de l'environnement d'exploitation.

Options disponibles

Coconut-shell or coal-based carbonBox or V-bank geometryScrim-controlled low-dust constructionHeader or box-frame mounting

Planning a VOC Molecular Air Filter specification?

Envoyez-nous vos dimensions, conditions d'installation, objectifs de performance et finition de surface requise.