An airtight metal-to-fabric-to-metal connector that interrupts vibration transmission between fans, air-handling equipment and rigid ductwork.
  • Vibration-Isolating Fabric
  • Airtight Double-Lock Seams
  • Galvanized Metal Edges
  • Oil and Moisture Resistant
Demander un devis. Browse les produits

Introduction de produit

A neoprene flexible duct connector places a coated woven fabric strip between two galvanized sheet-metal edges. One metal edge is formed into the equipment transition and the other into the connected duct, leaving the fabric free to flex without carrying rigid vibration. The polychloroprene-coated fiberglass fabric resists moisture, weathering and many oils encountered in plant rooms. Factory double-lock seams hold the fabric evenly and avoid exposed punctures through the active flexible width.

Key Features

The compliant neoprene strip breaks the solid metal path that transmits fan and blower vibration.

Woven fiberglass reinforcement controls fabric stretch under alternating positive and negative pressure.

Factory double-lock seams capture the coated fabric without field stitching or loose fasteners.

Galvanized metal edges integrate directly into rectangular or round sheet-metal transitions.

Préoccupations du client produit

A flexible connector must move freely while remaining airtight; excess tension, sag or misalignment can turn the fabric into a load-bearing duct component.

Fan vibration travels through rigid ductwork into occupied clean spaces.The reinforced elastomer fabric interrupts the metal path adjacent to the equipment.
An undersized fabric width is pulled tight when the fan starts.Adequate exposed width and neutral alignment preserve movement in every operating mode.
Field screws puncture the active fabric and create leakage points.Factory metal-to-fabric lock seams keep fasteners outside the flexible center section.
Oil mist or humid air degrades a general-purpose canvas strip.Polychloroprene-coated fiberglass provides stronger moisture and oil resistance for plant-room duty.

Les applications typiques

Air-handling-unit connectionsSupply and exhaust fan outletsFan-coil and terminal-unit connectionsVibration-isolated plenumsPump-room and laboratory exhaust equipment

Paramètres techniques

Typical construction data for factory-seamed neoprene flexible duct connector are listed below.

Matériaux de baseWoven fiberglass fabric double-coated with polychloroprene
Panneau épaisseur0.60–0.75 mm coated fabric
Largeur effective75–150 mm exposed flexible fabric width
Longueur maximale30000 mm supplied coil length
Acier face épaisseur0.45–0.60 mm galvanized steel edge strips
Densité CoreApproximately 1000–1100 kg/m³ polychloroprene compound
Conductivité thermiqueApproximately 0.20–0.25 W/(m·K) for coated elastomer fabric
surface finieBlack neoprene coating with bright galvanized steel edges
Type jointFactory double-lock metal-to-fabric seam; formed or flanged metal duct connection
CustomisationDisponible en fonction de l'application prévue et de l'environnement d'exploitation.

Options disponibles

Neoprene, silicone or PTFE-coated fabricGalvanized, aluminum or stainless metal edges75–150 mm active fabric widthStraight coil or prefabricated rectangular connector