클린룸 장비 및 무균 시설 필수품의 원스톱 공급업체국제 프로젝트 지원
Open mobile navigationClose mobile navigation
/ 제품 / 클린룸 장비 예비 부품 / AHU Replacement Filter
클린룸 장비 예비 부품

AHU 교체 필터

A rigid-header six-pocket air filter for replacing an established particulate stage in cleanroom and process air-handling units without changing the filter housing.
  • Six Tapered Filter Pockets
  • Rigid Galvanized Header
  • Extended Media Area
  • Matched Gasket Options
견적 요청 제품 찾아보기

상품 소개

The AHU replacement filter is an extended-surface pocket filter installed in a front- or side-access filter bank. Six tapered glass-fiber bags increase usable media area behind a standard square header while internal seams keep the pockets separated as airflow develops. A folded galvanized-steel frame holds the pocket mouths square, and a continuous perimeter gasket can seal the header against the retaining frame. Replacement selection must reproduce the existing face dimensions, pocket depth, filter stage, airflow direction and gasket location so the new filter seats correctly without bypass or interference inside the air-handling unit.

주요 기능

Six tapered pockets distribute airflow across an extended media area while retaining a compact standard header face.

The folded galvanized-steel header resists handling distortion during removal, transport and clamping in the filter bank.

Separated pocket seams reduce crowding between adjacent bags and preserve open media area under operating airflow.

Optional flat perimeter gaskets support a continuous compression seal on the specified upstream or downstream header face.

고객 제품 관심사

A pocket filter can fit the opening yet still perform poorly when its depth, pocket layout or sealing arrangement differs from the original module.

An incorrect face size or header depth prevents the replacement from seating beneath the existing clamps.Module width, height, header depth and retaining-frame clearance are matched to the removed filter before manufacture.
Bags that are too long can contact coils, dampers or the next filter stage inside a shallow AHU section.Pocket depth and installed airflow direction are selected to preserve the measured downstream service clearance.
A missing or misplaced gasket allows unfiltered air to bypass the media around the header.Gasket material, face location and continuity are configured for the actual sealing surface in the filter bank.
Poor pocket separation causes adjacent bags to crowd together and reduces effective media exposure.Tapered pocket geometry and continuous internal separators hold six flow paths open across the module.

일반적인 응용 프로그램

Cleanroom make-up and recirculation AHUsProcess ventilation filter banksHEPA prefiltration stagesCommercial and industrial HVAC maintenance

기술 매개변수

The ranges below describe common rigid-header pocket filters used as replaceable AHU stages; final dimensions and media selection are matched to the installed filter bank.

핵심 재료Air-laid glass-fiber pocket media with galvanized-steel header and optional elastomer perimeter gasket
패널 두께20-25 mm nominal folded header depth
유효 폭287-592 mm nominal filter module width
최대 길이Up to 640 mm pocket depth
강철 면면 두께0.5-0.8 mm nominal galvanized-steel header sheet
코어 밀도16-40 kg/m³ for representative low-density bonded glass-fiber media
열전도도 (Thermal Conductivity)0.032-0.046 W/(m·K) for representative low-density glass-fiber media
표면 마무리Natural galvanized-silver header, clean white glass-fiber pockets and optional black flat gasket
접합 유형Sealed six-pocket assembly retained in a folded double-U header with compression-gasket seating
사용자 정의의도된 응용 프로그램 및 운영 환경에 따라 사용할 수 있습니다.

사용 가능한 옵션

Matched full-size or half-size module370-640 mm pocket depthAlternative pocket count and media gradeUpstream, downstream or circumferential gasket

Planning a AHU Replacement Filter specification?

치수, 설치 조건, 성능 목표 및 필요한 표면 마감을 보내십시오.

우리 팀과 대화하십시오.
저희에게 이메일 whatsapp WeChat

제품

뉴스

회사 소개

문의하기