Pemasok One-Stop Anda untuk Peralatan Cleanroom dan Fasilitas Aseptik EsensialDukungan proyek internasional
Open mobile navigationClose mobile navigation
Cleanroom HVAC dan Peralatan Penanganan Udara

Hot-Water Heating Coil (Kopil Pemanas Air Panas)

A multi-row copper-tube coil that transfers boiler or heat-pump hot water into cleanroom supply and reheat air streams.
  • Multi-Row Hydronic Transfer
  • Low-Temperature Water Ready
  • Vent and Drain Access
  • Counterflow Circuiting
Permintaan untuk kutipan Browse Produk

Perkenalan produk

Hot water passes through copper circuits expanded into aluminum fins, creating a large air-side transfer surface within a flanged casing. Separate supply and return headers distribute flow across the face, and vents at high points remove trapped air. Row count, fin pitch and circuiting can be selected for conventional boiler water or lower-temperature heat-pump loops.

Fitur utama:

Copper tubes and aluminum fins combine high thermal conductivity with widely available service materials.

Counterflow circuiting maintains useful mean temperature difference across multiple rows.

Header vents and low-point drains support filling, air removal and seasonal service.

Fin spacing and protective coatings can be matched to filtration level and cleaning method.

Kekhawatiran produk pelanggan

Hydronic heating coils must deliver the required capacity at available water temperature without excessive water or air pressure drop.

Low-temperature hot water cannot heat through an undersized coil face.Additional rows and optimized circuiting provide more transfer area at a smaller water-air temperature difference.
Trapped air blocks circuits and creates cold sections.High-point automatic or manual vents release air from both supply and return headers.
High water velocity causes erosion and noise.Circuit quantity is selected to keep tube velocity within a stable hydronic range.
Tight fin spacing clogs before scheduled filter maintenance.A suitable fin pitch balances heat-transfer area with cleanability and face pressure drop.

Aplikasi yang Tipis

Cleanroom supply-air heatingHeat-pump hot-water AHUsHospital ventilation heatingPharmaceutical temperature controlLaboratory make-up air

Parameter teknis

Representative material and dimensional ranges for an AHU hot-water coil are listed below.

Bahan intiCopper tubes mechanically expanded into aluminum fins with copper headers
Ketebalan Panel (Panel Thickness)1.2-2.0 mm galvanized steel casing
Efektif lebar300-2600 mm active coil face width
Panjang maksimumUp to 3800 mm overall casing length
Baja menghadap ketebalan1.2-2.0 mm galvanized or 304 stainless frame
Kepadatan inti (core density)Approximately 2730 kg/m³ for the 3003 aluminum fin stock used across the multi-row hot-water coil
Konduktivitas Termal (Thermal Conductivity)Approximately 193 W/(m·K) for 3003 aluminum hot-water coil fins at room temperature
Permukaan selesaiNatural or hydrophilic-coated aluminum fins with galvanized casing
Jenis BersamaBrazed copper tube/header joints with flanged casing and threaded water ports
Customization (Kustomisasi)Tersedia berdasarkan aplikasi yang dimaksudkan dan lingkungan operasi.

Pilihan yang tersedia

One to twelve rowsDifferent copper tube diameters and circuitsAluminum, copper or epoxy-coated finsStainless casing, vents, drains and freeze-stat pocket