Pemasok One-Stop Anda untuk Peralatan Cleanroom dan Fasilitas Aseptik EsensialDukungan proyek internasional
Open mobile navigationClose mobile navigation
Beranda / Produk / Sistem Distribusi Udara Cleanroom / Duct Airflow Measuring Station
Sistem Distribusi Udara Cleanroom

Stasiun Pengukuran Aliran Udara Duct

A permanently installed multi-point sensing assembly that converts representative duct velocities into continuous volumetric airflow and temperature data.
  • Multi-Point Velocity Traverse
  • Low-Airflow Measurement
  • Remote Digital Transmitter
  • Supply or Exhaust Monitoring
Permintaan untuk kutipan Browse Produk

Perkenalan produk

The duct airflow measuring station uses several bead-in-glass thermal sensors distributed across the duct cross-section to capture a representative velocity traverse. Each node compares a heated element with a reference temperature element, and the remote transmitter combines the readings with the entered duct area to calculate volumetric or mass airflow. Stainless-steel probes, plenum-rated cables and an external display enclosure suit permanent installation where operators need more than a one-time balancing reading. Analog and network outputs can feed room-pressure control, air-change verification or maintenance trending.

Fitur utama:

Multiple independently calibrated sensing nodes reveal an uneven velocity profile that a single-point probe can miss.

Thermal-dispersion measurement operates at the low duct velocities common in ventilation and pressure-tracking branches.

A remote transmitter displays airflow and temperature while isolating electronics from the active duct section.

Selectable analog and serial communications support connection to airflow alarms or a building control system.

Kekhawatiran produk pelanggan

Reliable airflow control depends on a measurement point that represents the whole duct profile and remains stable at low velocity.

An elbow or transition creates a skewed velocity profile across the measuring plane.A multi-node probe array averages velocities over the duct area instead of reporting one unrepresentative point.
Pitot-style pressure signals become too small for dependable low-flow tracking.Thermal-dispersion sensor nodes retain useful resolution at substantially lower air velocities.
A failed probe remains unnoticed while the control loop continues using a false total.Node-status diagnostics and configurable alarms identify sensor or transmitter faults for maintenance.
Temporary balance readings do not show later drift caused by filter or fan changes.Permanent measurement provides continuous total airflow and a recordable signal for trend comparison.

Aplikasi yang Tipis

Cleanroom supply-air verificationReturn and exhaust airflow trackingLaboratory pressure-control systemsOutdoor-air delivery monitoringAir-change-rate performance trending

Parameter teknis

Typical construction and dimensional ranges for a permanent multi-point duct airflow station are listed below.

Bahan inti304 stainless-steel probe tubes with hermetically sealed thermistor nodes and plenum-rated sensor cables
Ketebalan Panel (Panel Thickness)1.0–2.0 mm stainless probe supports and mounting plates
Efektif lebar100–2500 mm duct traverse width using one or more probes
Panjang maksimumUp to 2500 mm active probe length for rectangular duct arrays
Baja menghadap ketebalan1.0–2.0 mm stainless mounting flange and probe bracket
Kepadatan inti (core density)Approximately 8000 kg/m³ for 304 stainless-steel probe components
Konduktivitas Termal (Thermal Conductivity)Approximately 14–16 W/(m·K) for 304 stainless-steel probe components
Permukaan selesaiClean passivated stainless probes with powder-coated remote transmitter enclosure
Jenis BersamaDuct-insertion compression flange with sealed cable glands to a remote transmitter
Customization (Kustomisasi)Tersedia berdasarkan aplikasi yang dimaksudkan dan lingkungan operasi.

Pilihan yang tersedia

Round-duct single-probe configurationRectangular multi-probe traverse arrayAnalog 0–10 V or 4–20 mA outputsBACnet or Modbus communication interface

Planning a Duct Airflow Measuring Station specification?

Kirimkan kami dimensi Anda, kondisi instalasi, target kinerja dan permukaan akhir yang diperlukan.

Bicaralah dengan tim kami
Email Kami WhatsApp WhatsApp WhatsApp WhatsApp WeChat adalah