Humidificateur Steam Cylinder
- Complete Electrode Vessel
- Integrated Steam Outlet
- Plug-In Terminal Layout
- O-Ring Drain Interface
Introduction de produit
The humidifier steam cylinder is the removable evaporation vessel at the center of an electrode steam humidifier. Conductive feedwater carries current between the installed metal electrodes, heating the water directly and releasing atmospheric steam through the molded top outlet. The cylinder also groups the power terminals, high-water sensing connection, fill path and bottom drain-valve interface into one service component. Replacement selection must match the humidifier model, steam capacity, supply voltage and phase, electrode arrangement, steam-hose connection and drain seat because cylinders with a similar external size can have different internal and electrical configurations.
Key Features
Integrated electrode grids provide the immersed current path required by a compatible conductive-water steam generator.
Color-separated power terminals and a distinct sensor connection support orderly reconnection to the humidifier wiring harness.
A molded steam outlet and O-ring-sealed bottom drain interface allow the complete evaporation chamber to be removed as one service part.
Préoccupations du client produit
A replacement cylinder must reproduce the original hydraulic, mechanical and electrical interfaces while remaining suitable for the actual supply water and steam duty.
Les applications typiques
Paramètres techniques
The ranges below describe common molded replacement cylinders used in commercial electrode steam humidifiers; the exact cylinder is selected for the compatible equipment model.
| Matériaux de base | Translucent heat-resistant polymer vessel with stainless steel electrodes, molded engineering-polymer cap and elastomer seals |
|---|---|
| Panneau épaisseur | 3-8 mm nominal molded vessel-wall and cap section |
| Largeur effective | 140-300 mm nominal cylinder outside diameter |
| Longueur maximale | Up to 650 mm overall height including steam outlet and drain interface |
| Acier face épaisseur | 1.0-3.0 mm nominal stainless steel electrode-grid thickness |
| Densité Core | Approximately 1190-1210 kg/m³ for representative transparent polycarbonate vessel grades |
| Conductivité thermique | Approximately 0.20 W/(m·K) for representative transparent polycarbonate vessel material |
| surface finie | Smooth translucent clear or pale-blue vessel with dark molded cap and color-identified terminal insulators |
| Type joint | Molded sealed vessel with plug-in electrode terminals, hose-clamped steam outlet and O-ring-seated bottom drain bayonet |
| Customisation | Disponible en fonction de l'application prévue et de l'environnement d'exploitation. |
Options disponibles
Planning a Humidifier Steam Cylinder specification?
Envoyez-nous vos dimensions, conditions d'installation, objectifs de performance et finition de surface requise.

Anglais
Allemand
Arabe
FrançaisCurrent
Indonésien
Japonais
Coréen
Le malais
Le portugais
russe
espagnol
Thaïlandais
Le turc
Le vietnamien