A compact mini-pleat final filter that restores high-efficiency particle filtration in an existing cleanroom fan filter unit.
  • Dense Mini-Pleat Media
  • Low-Profile FFU Frame
  • Sealed Perimeter Pack
  • Matched Gasket Interface
견적 요청 제품 찾아보기

상품 소개

The FFU HEPA filter is the final air-cleaning element installed beneath the fan section of a fan filter unit. Fine glass-fiber media is formed into closely spaced mini-pleats and stabilized with hot-melt separators to provide a large filtration area within a shallow frame. Perimeter potting prevents bypass between the media pack and aluminum frame, while a compression gasket seals the filter against its supporting surface. Replacement size, efficiency class, pressure drop, gasket side and airflow direction must match the original FFU design.

주요 기능

Mini-pleat construction provides high media area within a shallow FFU profile.

Continuous perimeter potting closes the leakage path between media and frame.

A fitted compression gasket seals the filter to the FFU housing or ceiling interface.

Protective face grids reduce accidental pleat damage during handling and installation.

고객 제품 관심사

A replacement HEPA panel must fit the FFU precisely while preserving airflow and eliminating bypass around the media pack.

A frame with incorrect dimensions leaves gaps or cannot enter the FFU housing.Face size, depth and corner tolerances are matched to the original filter envelope.
An unsuitable pressure drop reduces delivered cleanroom airflow.Media area and pleat geometry are selected for the FFU operating face velocity.
Air bypasses the media through an incompatible gasket arrangement.Gasket material, width, thickness and upstream or downstream position are matched to the sealing surface.
Pleats are damaged during overhead handling and replacement.Optional upstream and downstream protective grids shield the media without blocking its open area.

일반적인 응용 프로그램

Cleanroom fan filter unitsLaminar-flow ceiling modulesMini-environment final filtrationFFU filter replacement programs

기술 매개변수

Typical construction ranges for replacement FFU mini-pleat HEPA filters are shown below.

핵심 재료Water-resistant micro-glass-fiber HEPA media with hot-melt mini-pleat separators
패널 두께50-120 mm nominal filter depth
유효 폭305-610 mm nominal face width
최대 길이최대 1220 mm 공칭 면 길이
강철 면면 두께0.4-0.8 mm optional galvanized-steel protective grid wire or sheet
코어 밀도Approximately 80-150 kg/m³ nominal pleated media-pack bulk density
열전도도 (Thermal Conductivity)Approximately 0.035-0.050 W/(m·K) for the dry glass-fiber media pack
표면 마무리Natural anodized-aluminum frame with white media and dark-gray closed-cell gasket
접합 유형Mini-pleat pack continuously potted into a mitered frame with compression-gasket seal
사용자 정의의도된 응용 프로그램 및 운영 환경에 따라 사용할 수 있습니다.

사용 가능한 옵션

Matched HEPA efficiency classUpstream or downstream gasketSingle or double protective gridCustom FFU face size and depth