ST / INTEGRATED CLEANROOM PROCUREMENTEquipment / Consumables / Supporting facilities
PRODUCT / TECHNICAL DATA Modular Cleanroom SystemsSpecifications / Configurations / Procurement

Modular Cleanroom Systems

575 × 575 × 310 mm FFU — Aluminum Impeller

Product specifications

Overall dimensions (L × W × H)575 × 575 × 310 mm
Filter dimensions570 × 570 × 69 mm
ImpellerAluminum
Housing materialAluminum-zinc-coated steel (Aluzinc)
Reference airflow range600–800 m³/h
Motor power220 W
Reference power supplyAC 220 V, 50 Hz
Speed controlThree-speed adjustment
Filter mediaGlass fiber; final performance specified for the application
Reference noise52 ± 3 dB at 0.45 m/s
Reference face velocity0.45 m/s; operating duty to be confirmed for the selected configuration
InstallationSeparate fan unit and filter; supporting frame and sealing arrangement required

Customization availableSpecifications can be customized to your requirements.

Request a quotation

Specify the quantity and configuration in your inquiry.

575 × 575 × 310 mm FFU — Aluminum Impeller provides a compact filtered-air supply point in the deeper 310 mm housing configuration. The separate glass-fiber filter is selected for the process requirement.

Reserve space for the deeper assembly and a filter-removal route around fixed equipment.

APPLICATION ENVIRONMENTS

Applications

01

Inspection clean benches

Supply compact inspection benches with the filter efficiency and airflow selected for the task.

02

Small cleanroom booths

Provide roof-mounted filtered air above preparation or handling work inside small booths.

PRACTICAL BENEFITS

Key features

Separate the outline from service space

Allowing space for the filter frame and removal route keeps the unit serviceable.

Commission the selected configuration

Three-speed control supports adjustment with the ordered filter installed.

CHOOSING THE ASSEMBLY

Selection

Above and below the ceiling

Check headroom, inlet space and filter access above permanent equipment.

Required filtration

Specify filter performance alongside dimensions and required airflow.

PRODUCT QUESTIONS

Common questions

Is the square outline enough to confirm a replacement will fit?

No. Also check depth, supports, seals and the filter-removal route.

Can the dimensions and connection be customized?

Yes. Specify the available space, electrical connection and required filtration duty.

PROCUREMENT / INQUIRY

Request a
product quotation.

Tell us the quantity and configuration you need. This product will be included automatically.

Fields marked * are required.

YOUR PRODUCT575 × 575 × 310 mm FFU — Aluminum ImpellerReview specifications
Useful details for this quotation

Match the fan-filter unit to the ceiling opening, airflow requirement and control interface.

  • Ceiling grid and unit opening
  • Required supply airflow
  • Site power supply
  • Control arrangement

We use your contact details and requirements to review your inquiry and prepare a quotation. Sending this form does not place an order.

575 × 575 × 310 mm FFU — Aluminum Impeller — product view

YOUR PURCHASING BRIEF

Inquiry list

Collect products here, then send your requirements in one inquiry.

Continue to inquiry ↗

This list is saved in this browser. Adding a product does not place an order.